Научная статья на тему 'MOISTURE TRANSPORT IN THE VENTILATED CHANNEL WITH HEATING BY COIL'

MOISTURE TRANSPORT IN THE VENTILATED CHANNEL WITH HEATING BY COIL Текст научной статьи по специальности «Строительство и архитектура»

CC BY
27
5
i Надоели баннеры? Вы всегда можете отключить рекламу.
Журнал
Magazine of Civil Engineering
Scopus
ВАК
RSCI
ESCI
Ключевые слова
BUILDINGS / VENTILATED FACADES / MOISTURE TRANSPORT / FACING LAYER / THERMAL INSULATION / HEATING COIL / AIR GAP

Аннотация научной статьи по строительству и архитектуре, автор научной работы — Statsenko E.A., Musorina T.A., Ostrovaia A.F., Olshevskiy V., Antuskov A.L.

This article considers the moisture transport phenomenon in the vertical ventilated channel. HVF construction parameters are determined influencing the rate of moisture transport. It is necessary to have h ≤ L/25 ≈ 8 cm. The greatest air movement is created in the construction with the open rustications. The optimal location of the heat sources on the channel height, as well as their favorable combination from the point of view for the process of drying the outer surface of the thermal insulation material, was identified. The air velocity dependences on height of an air gap are determined and it was found that the greatest values taken at the maximum height velocity. Ratio between the moisture transport and the distance to the heat source is installed. Drying processes are compared with the various combinations of heat sources. The direct dependence of the vaporation weight rate of the time is installed.

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

ВЛАГОПЕРЕНОС В ВЕНТИЛИРУЕМОМ КАНАЛЕ С НАГРЕВАТЕЛЬНЫМ ЭЛЕМЕНТОМ

В данной статье изучается явление влагопереноса в вертикальном вентилируемом канале. Определяются параметры конструкции НВФ, оказывающие влияние на скорость влагопереноса. Необходимо иметь h ≤ L/25 ≈ 8 см. Наибольшее движение воздуха создается в конструкции с открытыми рустами. Выявлено оптимальное расположение источников тепла по высоте канала, а также их выгодные сочетания с точки зрения процесса высушивания наружной поверхности теплоизоляционного материала. В результате исследования скорости движения воздуха по высоте вентилируемого зазора, было установлено, что на максимальной высоте скорости принимают наибольшие значения. А также выведено соотношение между массовой скоростью переноса влаги и расстоянием до источника тепла. Сравниваются процессы высушивания при различных сочетаниях нагревательных элементов. Установлена прямая зависимость массовой скорости испарения от времени.

Текст научной работы на тему «MOISTURE TRANSPORT IN THE VENTILATED CHANNEL WITH HEATING BY COIL»

doi: 10.18720/MCE.70.2

Moisture transport in the ventilated channel with heating by coil

Влагоперенос в вентилируемом канале с нагревательным элементом

E.A. Statsenko, T.A. Musorina, A.F. Ostrovaia, V.Ya. Olshevskiy, A.L. Antuskov,

Peter the Great St. Petersburg Polytechnic University, St. Petersburg, Russia

Студент Е.А. Стаценко, студент Т.А. Мусорина, студент А.Ф. Островая, аспирант В.Я. Ольшевский, студент А.Л. Антуськов, Санкт-Петербургский политехнический университет Петра Великого, г. Санкт-Петербург, Россия

Key words: buildings; ventilated facades; moisture transport; facing layer; thermal insulation; air gap; heating coil

Ключевые слова: здания; вентилируемый фасад; влагоперенос; облицовочный слой; теплоизоляция; воздушный зазор; нагревательный элемент

Abstract. This article considers the moisture transport phenomenon in the vertical ventilated channel. HVF construction parameters are determined influencing the rate of moisture transport. It is necessary to have h < L/25 = 8 cm. The greatest air movement is created in the construction with the open rustications. The optimal location of the heat sources on the channel height, as well as their favorable combination from the point of view for the process of drying the outer surface of the thermal insulation material, was identified. The air velocity dependences on height of an air gap are determined and it was found that the greatest values taken at the maximum height velocity. Ratio between the moisture transport and the distance to the heat source is installed. Drying processes are compared with the various combinations of heat sources. The direct dependence of the vaporation weight rate of the time is installed.

Аннотация. В данной статье изучается явление влагопереноса в вертикальном вентилируемом канале. Определяются параметры конструкции НВФ, оказывающие влияние на скорость влагопереноса. Необходимо иметь h < L/25 = 8 см. Наибольшее движение воздуха создается в конструкции с открытыми рустами. Выявлено оптимальное расположение источников тепла по высоте канала, а также их выгодные сочетания с точки зрения процесса высушивания наружной поверхности теплоизоляционного материала. В результате исследования скорости движения воздуха по высоте вентилируемого зазора, было установлено, что на максимальной высоте скорости принимают наибольшие значения. А также выведено соотношение между массовой скоростью переноса влаги и расстоянием до источника тепла. Сравниваются процессы высушивания при различных сочетаниях нагревательных элементов. Установлена прямая зависимость массовой скорости испарения от времени.

Introduction

In the design of these systems radically affected increasing requirements for heat transmission resistance of enclosure structures. It is a practical impossibility to create a high-quality enclosing parts without using effective thermal insulation materials.

Clearly, the most favorable location of the thermal insulation in the design is its location at the outer surface. This ensures the offset of dewpoint temperature in the stream.

This is the principle used in the HVF constructions.

Fiber thermal insulation material having a high air permeance is most popular for the HVF constructions.

Modern fibrous mineral-cotton materials have low density, their use is economic. The lower the density of the mineral wool, the higher its air permeance. This parameter has an effect on moisture removal rate from the ventilated gap.

The moisture transport is the process of the movement of moisture which represents transfer of vacant and physically-bounded water under the influence of gravitational and sorption (molecular and capillary) forces.

The control of moisture level is necessary is necessary to create an optimum operating conditions of the ventilated facade. The timely identification of excessive moisture appearance sources avoids the adverse effects of excessive moistening such as corrosion of metal products and parts, destruction of concrete, stone and brickwork during freezing and thawing, the color change of the building architectural detail, biological damage and deterioration of thermal properties.

Thus, quantitative calculation of moisture transfer is one of the most important in the multilayered enclosure structure designing.

This article conditions conducive to the most optimal process of removing moisture from the hinged ventilated facade gap by simulating moisture transport processes in different parameters HVF model are formulated.

A special contribution to the study of moisture transport process in the vertical ventilated channel was made by [1-24].

In this work [1] is investigated the impact of the presence of the technological gaps (rustication) the rate of air flow in the gap. The speed dependence on the width of the ventilated gap is established empirically for the construction with open and closed rustications.

The authors identify in the article [2] the conditions under which there is a cold air filtration in the ventilated gap. The publication [3] considers features of work of facades with and without rustications. The article [11] is assessed the effect of moisture transport on the dispersed and cellular materials. The authors of the publication [14] define adequate existence conditions of the free convection stream in the vertical conduit. In the work [22] consider issues of a natural ventilation of the vertical channel. In the work [27] the wall building with the ventilated facade thermal protection taking into account a longitudinal air filtration are investigated.

Purpose and goals of article are:

- to determine the most effective combination of heat sources depending on the air velocity in the gap.

- to consider the influence of the sources location of mechanical heat on the moisture transfer in the HVF gap.

- to determine the mass rate of moisture vaporization.

- to identify the mass velocity dependence on the distance from the heat source.

Methods and Results

The imperfection of building structures leads to their excessive moistening. Therefore, more and more attention is given to the moisture accumulation ability of materials and the possibility of their drying out. The majority of the moisture control methods are focused on reducing the heat- and moisture input into the air gap.

The main reason for the movement of moisture in the HVF construction is a difference of humidity, temperature and differential pressure of the air-steam mixture in the material. A zone of the greatest moistening is the layer of a mineral wool heat insulation adjoining the gap. Let us consider its rate of drying for different parameters HVF design.

To identify the optimal design parameters for the study of moisture vented we will consider the stylized scheme of the ventilated gap between the "hot" plane y = 0 (with Th = 67 °C) and the cold plane y = h (with Tc = 22 °C).

Heating is provided with three heating elements located throughout the height of the installation. For equal distribution of heat elements attach to a tin sheet, therefore Th = const. The model height is equal to L = 204 cm, and L » h. While producing a facade sample we consider the temperature

difference of external and internal layers proved by performance of heating systems. The model considers wall heating and heat input from it in the air layer. The external air is supposed to come into the air layer through the lower air hole. It rises through the ventilated channel and leaves through the top air holes. Air temperature increases and its relative moisture changes during the rise. At the same time moisture increases throughout the height of the layer [1]. To conduct this experiment a different combination of heat sources: "lower-middle", "lower-upper", "middle-upper" are used.

To identify an optimum variant for the study of moisture transport construction it is necessary to know the air velocity in the gap. It depends on the supply air method into the installation - with open or pressurized rustications.

Let us carry out an experiment. We measure the air velocity inside the HVF model depending on the gap width with and without rustications with various combinations of heat sources. We use thermal anemometer for measurement.

0.4 035 0.3 0.2S 0.2 015 01 005 0

■0.05

—4

а-.

'—4

*

л

0_s ! 4 1 > 8 10 12 14 16 18 2 0 22

lower-upper i lower-middle i middle-upper

Figure 1. Sealed rustications

0.4 0.35 0.3 0.25 0.2 0.15 0.1 0.05 0

»

J t А \

* A i L_ 14

A

I 1 A A

• lower-upper ■ lower-middle a middle-upper

2 4 6 8 10 12 14 16 18 20 22 h

Figure 2. Open rustications

From the resulting graphs it follows that:

- the most air movement is created in the open rustications, because of the greater volume of heated air, as well as of various combinations of heat sources.

- in the design with a sealed rustications - "perfect channel" - is the air volume is less because the current is only from the bottom, reducing the drying speed.

- the most disadvantageous of the considered combination is the combination of heating elements - "middle-upper". This is due to the fact that the air is not heated when entering to the canal at the bottom of the battery, and there is no difference in temperature, therefore, there is no active air movement. Basically, the current is through the rustications, involving the construction of cold air. At the same time the height velocity decreases and tends to zero when large gaps.

We will use mineral-cotton samples 95 x 210 x 50 mm for further experience. The dry sample weight is 140 g. The wetted sample weight is 160 g.

We will put the first sample in the HVF air gap with a combination of batteries "lower-middle", the second sample with a combination of "lower-upper" and will consistently record the mass at regular intervals under the above combinations of heating elements.

To simulate channel is necessary to have L/h >25, cm [1].

We will find a mass rate of vaporization for each measurement:

Am

*

m =-

At

(1)

where Am - the mass difference of two consecutive measurements, At - the interval between measurements, At = 600 s.

We will construct a dependency graph of the mass velocity m* on the distance from a moisture source for height z to of the heating element.

Figure 3. The dependency graph of the mass velocity on the distance from a moisture source for height.

It can be observed that in the case when the lower battery is disconnected, the current is not carried out, the mass transfer rate in the model equivalent to the mass transfer rate in natural conditions, therefore, the chosen combination is enabled the lower heat source are optimal.

Thus, it was established that the combination of "lower-middle", "lower-upper" with open rustications are the best for mass transfer mechanisms studying in the HVF construction.

The average mass rate of vaporization are:

„ Am _ 13 At = 5400 Am 14

m2 At 5400

= 0.0024, combination of "lower-middle", = 0.0026 combination of "lower-upper".

Thus, it was established that the maximum mass transfer rate is observed at the open rustications.

0 007

0 006

0 005

0004

0 003

0 002

0 001

v J- \

■ -

♦J ■ ■

♦ —•— — -- 9 _»

10

i lower-upper > lower-m

ddle

15

25

35

45

55

65

75* t

Figure 4. Dependence of m*on t

Thus, it was established that the maximum mass transfer rate is observed at the open rustications.

iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.

Obviously, the rate of vaporization repeated the air velocity. The greater the air velocity, the greater the rate of vaporization.

The highest velocity values were observed when combinations of heat sources "lower-upper".

We give a graph of air velocity in the HVF gap on the installation height.

Figure 5. Dependence air velocity in the HVF gap on the installation height

Based on the obtained results, it may be concluded that that the greatest values taken at the maximum height of the velocity. Therefore, the installation upper part is the most favorable location for the study of mass transfer.

Discussion

The great bulk of work on this topic is aimed at the moisture transport mechanisms study from the point of view of physics, practical tests was conducted [10, 25-26]. In this article the emphasis is placed on the experimental determination of the air flow dependences in the ventilated facade channel.

In the articles of other authors on the same topic is assumed constant the temperature of the warm surface wall (Th = const), whereas in this study the effect of the variable position of the heat sources.

Conclusions

Building humidity control is a key condition of increase of their durability, effective use and a healthy microclimate.

On the ground of the experiments we draw the following conclusions:

- the greatest air movement is created in the construction with the open rustications because of larger volume of heated air, as well as the use of different heat combinations, which contributes to the process of moisture transfer.

- the heating the air at the entrance of channel is not when the heat source is off , and there is no difference in temperature, consequently, there is no active air movement.

- the greatest values taken at the maximum height velocity.]

References

Musorina T., Olshevskyi V., Ostrovaia A., Statsenko E. Experimental assessment of moisture transfer in the vertical ventilated channel. MATEC Web of Conferences, TPACEE. 2016. Vol. 73. Pp. 02002. Nemova D.V., Olshevskyi V.Ja., Cejtin D.N. Gidrostatika termogravitacionnoj konvekcii v vertikal'nom kanale [Hydrostatics of thermogravitational convection in the vertical channel]. Nauchno-tehnicheskie vedomosti

Литература

Musorina T., Olshevskyi V., Ostrovaia A., Statsenko E. Experimental assessment of moisture transfer in the vertical ventilated channel // MATEC Web of Conferences, TPACEE 2016. Vol. 73. Pp. 02002. Немова Д.В., Ольшевский В.Я., Цейтин Д.Н. Гидростатика термогравитационной конвекции в вертикальном канале // Научно-технические ведомости Санкт-Петербургского государственного

SPBGPU. 2013. No. 4-1 (183). Pp. 295-301. (rus)

3. Vatin N., Petrichenko M., Nemova D., Staritcyna A., Tarasova D. Renovation of educational buildings to increase energy efficiency. Applied Mechanics and Materials. 2014. Vol. 633-634. Pp. 1023-1028.

4. Nemova D.V., Emel'janova V.A., Miftahova D.R. Jeksperimental'nye zadachi rascheta svobodnokonvektivnyh dvizhenij v navesnyh ventiliruemyh fasadah [Experimental problems of calculation the free-convection movements in the hinged ventilated facades]. Magazine of Civil Engineering. 2010. No. 8. Pp. 46-53. (rus)

5. Emel'janova V.A., Nemova D.V., Miftahova D.R. Optimizirovannaja konstrukcija navesnogo ventiliruemogo fasada [The optimized design of the hinged ventilated facade]. Magazine of Civil Engineering. 2014. No. 6. Pp. 67-74. (rus)

6. Petrichenko M.R. Convective heat and mass transfer in combustion chambers of piston engines. Basic results. Heat transfer. Soviet research. 1991. Vol. 5. No. 23. Pp. 703-715.

7. Ostrovaja A.F., Petrichenko M.R., Stacenko E.A. The glass ventilated facades. Research of an air gap. Applied Mechanics and Materials. 2015. Pp. 725-726.

8. Petrichenko M.R. Rasshcheplyayushchie razlozheniya v predel'nyh zadachah dlya obyknovennyh kvazilinejnyh differencial'nyh [The splitting decomposition in limit tasks for the ordinary quasilinear differential equations]. Second Edition St. Petersburg State Polytechnical University Journal. Physics and Mathematics. 2012. Pp. 143-149. (rus)

9. Petrichenko M.R., Petrochenko M., Yevtushenko E.B., Gidravlicheski optimal'naya ventiliruemaya shchel' [Hydraulically optimum ventilated gap]. Magazine of Civil Engineering. 2013. No. 2 (37). Pp. 35-40. (rus)

10. Vatin N., Petrichenko M., Nemova D. Hydraulic methods for calculation of system of rear ventilated facades. Applied Mechanics and Materials. 2014. Vol. 633-634. Pp. 1007-1012.

11. Gamajunov N.I., Gamajunov S.N. Massoperenos v poristyh i dispersnyh materialah [Mass transfer in porous and disperse materials]. Vestnik TvGTU. 2012. Vol. 22. No. 128. Pp. 46-54. (rus)

12. Kornienko S.V. Testirovanie metoda rascheta temperaturno-vlazhnostnogo rezhima ograzhdajushhih konstrukcij na rezul'tatah naturnyh izmerenij parametrov mikroklimata pomeshhenij [Testing of a method of calculation of temperature moisture conditions of the protecting designs on results of natural measurements of parameters of a microclimate of rooms]. Magazine of Civil Engineering. 2012. No. 2(28). Pp. 18-23. (rus)

13. Kornienko S.V. Kompleksnaja ocenka teplozashhity ograzhdajushhih konstrukcij obolochki zdanija [Complex assessment of a heat-shielding of the protecting building cover designs]. Magazine of Civil Engineering. 2012. No. 7. Pp. 43-49. (rus)

14. Petrichenko M.R., Petrochenko M.V. Dostatochnye uslovija sushhestvovanie svobodno-konvektivnogo techenija v vertikal'nom shhelevom kanale [Sufficient conditions existence of a free and convective current in the vertical slot-hole channel]. Nauchno-tehnicheskie vedomosti SPBGPU. 2012. No. 2. (rus)

15. Petrosova D.V. Neizotermicheskaja fil'tracija vozduha cherez ograzhdajushhie konstrukcii zamknutyh pomeshhenij [Not isothermal filtration of air through the protecting designs of the closed rooms]. Sankt-Peterburg, 2012. 118 p. (rus)

16. Yevtushenko E.B., Petrochenko M.V. Diffuzornaya konstrukciya navesnogo ventiliruemogo fasada [The diffuser design of ventilated facades]. Magazine of Civil

политехнического университета. 2013. № 4-1(183). С. 295-301.

3. Vatin N., Petrichenko M., Nemova D., Staritcyna A., Tarasova D. Renovation of educational buildings to increase energy efficiency // Applied Mechanics and Materials. 2014. Vols. 633-634. Pp. 1023-1028.

4. Немова Д.В., Емельянова В.А., Мифтахова Д.Р. Экстремальные задачи расчета свободноконвективных движений в навесных вентилируемых фасадах // Инженерно-строительный журнал. 2010. № 8. С. 46-53.

5. Емельянова В.А., Немова Д.В., Мифтахова Д.Р. Оптимизированная конструкция навесного вентилируемого фасада // Инженерно-строительный журнал. 2014. № 6. С. 67-74.

6. Petrichenko M.R. Convective heat and mass transfer in combustion chambers of piston engines. Basic results. Heat transfer // Soviet research. 1991. Vol. 5. № 23. Pp. 703-715.

7. Ostrovaja A.F., Petrichenko M.R., Stacenko E.A. The glass ventilated facades. Research of an air gap // Applied Mechanics and Materials. 2015. Vols. 725-726. Pp. 725726.

8. Петриченко М.Р. Расщепляющие разложения в предельных задачах для обыкновенных квазилинейных дифференциальных уравнений // Научно-технические ведомости Санкт-Петербургского государственного политехнического университета. 2012. С. 143-149.

9. Петриченко М.Р., Петроченко М.В., Явтушенко Е.Б. Гидравлически оптимальная вентилируемая щель // Инженерно-строительный журнал. 2013. № 2(37). С. 35-40.

10. Vatin N., Petrichenko M., Nemova D. Hydraulic methods for calculation of system of rear ventilated facades // Applied Mechanics and Materials. 2014. Vols. 633-634. Pp. 1007-1012.

11. Гамаюнов Н.И., Гамаюнов С.Н. Массоперенос в пористых и дисперсных материалах //Вестник ТвГТУ. 2012. № 128(22). С. 46-54.

12. Корниенко С.В. Тестирование метода расчета температурно-влажностного режима ограждающих конструкций на резкльтаттах натурных измерений параметров микроклимата помещений // Инженерно-строительный журнал. 2012. №. 2. С. 18-23.

13. Корниенко С.В. Комплексная оценка теплозащиты ограждающих конструкций оболочки здания // Инженерно-строительный журнал. 2012. №. 7. С. 4349.

14. Петриченко М.Р., Петроченко М.В. Достаточные условия существование свободно-конвективного течения в вертикальном щелевом канале // Научно-технические ведомости Санкт-Петербургского государственного политехнического университета. 2012. №. 2(147). С. 276-282.

15. Петросова Д.В. Неизотермическая фильтрация воздуха через ограждающие конструкции замкнутых помещений. Автореферат дисс на соиск. учен. степ. к.т.н.: Спец. 05.23.16. СПб: Сакнт-Петерубргский государственный политехнический университет, 2012. 118 с.

16. Явтушенко Е.Б., Петроченко М.В. Диффузорная конструкция навесного вентилируемого фасада // Инженерно-строительный журнал. 2013. № 8. С. 38-45.

17. Немова Д.В. Системы вентиляции в жилых зданиях как средство повышения энергоэффективности // Строительство уникальных зданий и сооружений. 2012. № 3. С. 84-86.

18. Петриченко М.Р., Петросова Д.В., Петроченко М.В. Фильтрационный перенос воздухом консервативной

Engineering. 2013. No. 8. Pp. 38-45. (rus)

17. Nemova D.V. Sistemy ventilyacii v zhilyh zdaniyah kak sredstvo povysheniya ehnergoehffektivnosti [Systems of ventilation in residential buildings as means of increase of energy efficiency]. Construction of Unique Buildings and Structures. 2012. Pp. 84-86. (rus)

18. Petrichenko M.R., Petrosova D.V., Petrochenko M.V. Fil'tracionnyj perenos vozduhom konservativnoj primesi (temperatury i teploty) skvoz' stenu [Filtrational transfer by air of conservative impurity (temperature and warmth) through a wall]. NTV SPbGPU. Fiziko-matematicheskie nauki. 2012. Pp. 68-72. (rus)

19. Darkwa J., Li J., Chow D.H.C. Heat transfer and air movement behaviour in a double-skin façade. Centre for Sustainable Energy Technologies (CSET). 2014. Pp. 198203.

20. Hana J., Lua L., Penga J. Hongxing Yanga Performance of ventilated double-sided PV facade compared with conventional clear glass façade. Energy and Buildings. 2013. Vol. 56. Pp. 204-209.

21. Bukhartsev V.N., Petrichenko M.R. Approximation of the depression curve of the inflow to an ideal trench. Power Technology and Engineering. 2011. No. 5. Pp. 374-377.

22. Rosca A.V., Pop I. Flow and heat transfer over a vertical permeable stretching/shrinking sheet with a second order slip. International Journal of Heat and Mass Transfer. 2013. Vol. 60. Pp. 355-364.

23. Barrios G., Huelsz G., Rechtman R., Rojas J. Wall/roof thermal performance differences between air- conditioned and non air-conditioned rooms. Energy and Buildings. 2011. Vol. 43. Pp. 219-223.

24. Gaillard L., Giroux-Julien S., Menezo C., Pabiou H. Experimental evaluation of a naturally ventilated PV double-skin building envelope in real operating conditions. Chair Habitats and Energy Innovations. 2012. Pp. 54-67.

25. Petrichenko M., Vatin N., Nemova D., Kharkov N., Korsun A. Numerical modeling of thermogravitational convection in air gap of system of rear ventilated facades. Applied Mechanics and Materials. 2014. Vols. 672-674. Pp. 19031908.

26. Olshevskyi V., Statsenko E., Musorina T., Nemova D., Ostrovaia A. Moisture transfer in ventilated facade structures. MATEC Web of Conferences. 2016. Vol. 53. Pp. 1-5.

примеси (температуры и теплоты) сквозь стену // Научно-технические ведомости Санкт-Петербургского государственного политехнического университета.

2012. № 4(159). С. 68-72.

19. Darkwa J., Li J., Chow D.H.C. Heat transfer and air movement behaviour in a double-skin façade // Centre for Sustainable Energy Technologies (CSET). 2014. Pp. 198203.

20. Hana J., Lua L., Penga J. Hongxing Yanga Performance of ventilated double-sided PV facade compared with conventional clear glass façade // Energy and Buildings.

2013. Vol. 56. Pp. 204-209.

21. Bukhartsev V.N., Petrichenko M.R. Approximation of the depression curve of the inflow to an ideal trench // Power Technology and Engineering. 2011. No. 5. Pp. 374-377.

22. Rosca A.V., Pop I. Flow and heat transfer over a vertical permeable stretching/shrinking sheet with a second order slip // International Journal of Heat and Mass Transfer. 2013. Vol. 60. Pp. 355-364.

23. Barrios G., Huelsz G., Rechtman R., Rojas J. Wall/roof thermal performance differences between air- conditioned and non air-conditioned rooms // Energy and Buildings. 2011. Vol. 43. Pp. 219-223.

24. Gaillard L., Giroux-Julien S., Menezo C., Pabiou H. Experimental evaluation of a naturally ventilated PV double-skin building envelope in real operating conditions // Chair Habitats and Energy Innovations. 2012. Pp. 5467.

25. Petrichenko M., Vatin N., Nemova D., Kharkov N., Korsun A. Numerical modeling of thermogravitational convection in air gap of system of rear ventilated facades // Applied Mechanics and Materials. 2014. Vols. 672-674. Pp. 19031908.

26. Olshevskyi V., Statsenko E., Musorina T., Nemova D., Ostrovaia A. Moisture transfer in ventilated facade structures // MATEC Web of Conferences. 2016. Vol. 53. Pp. 1-5.

Elena Statsenko,

+7(981)8398538; [email protected] Tatiana Musorina,

+7(952)2860376; [email protected] Anastasia Ostrovaia,

+7(953)3449063; [email protected]

Vyacheslav Olshevskiy, +7(911)9199526; [email protected]

Anton Antuskov,

+7(921)4257517; [email protected]

Елена Александровна Стаценко, +7(981)8398538; эл. почта: [email protected]

Татьяна Александровна Мусорина,

+7(952)2860376;

эл. почта: [email protected]

Анастасия Федоровна Островая, +7(953)3449063;

эл. почта: [email protected]

Вячеслав Янушевич Ольшевский, +79119199526;

эл. почта: [email protected]

Антон Леонидович Антуськов, +7(921)4257517;

эл. почта: [email protected]

© Statsenko E.A.,Musorina T.A.,Ostrovaia A.F.,Olshevskiy V.Ya.,Antuskov A.L., 2017

i Надоели баннеры? Вы всегда можете отключить рекламу.