Evaluation of Water Purification Plant at Kosti City - Sudan
r
Nahla Babiker Hussien Abdel Moneim Osman A. Babikr 1 Mortada H.A. Elhesain 1
Yasir A. Mohamed 1
[email protected] moneimosman4@gmail. com morta27666@gmail .com [email protected]
1 University of El Imam El Mahdi, Kosti, Sudan
Abstract. The objective of this study is to evaluate the purification level of water plant in Kosti city to supply water with high quality. This study was done to investigate the drinking water quality of Kosti city. Five sites of water network were selected, during March 2017
- May 2017. Thirty (30) samples of water from different areas of Kosti city were collected to evaluate water purification by using some laboratory tests for physical, chemical properties and microbiological. The results obtained showed that the turbidity level ranged between (4.2 - 150 NTU) thus exceeding the permissible level of WHO 1993 standards (5 NTU).The PH value was ranged between (6.3
- 8.2) and level of TDS (111 - 157 mg/L) ,hardness (43 - 89 mg/L) , residual chlorine (0.1 - 0.4 mg/L) , EC (116 - 234 ^s/cm) . All these values fall below the values of national and international standards of (WHO, 1993) and Sudanese Organization for Standardization and Metrology 2008. The level of COD (86 - 584.4 mg/L), BOD (16 -144mg/L). Biological tests were conducted to determine the presence of fecal coliform the results showed that the samples of water limits according to the specifications of the Sudanese Standards and
Metrology Organization (SSMO, 2008) and the World Health Organization (WHO, 1993) by 100%.._
Keywords: water, physical properties, chemical properties, microbiological, evaluation, purification plant
Introduction
Water is considered as the most essential element on earth for all kinds of living creatures to maintain their life. In many time with rapid urban and rural expansion, the demand for water supply has increased many times as a result of more water has been used in domestic, agriculture and industrial sectors. (Al-Jlil, et al, 2014).
Drinking water is the most important natural resource as only less than 1% of the total water on the planet is potable and accessible. Sustained supply of safe and potable drinking water is of paramount significance in promotion of health and well-being of the people. The performance evaluation of a treatment plant is a process to measure the functioning efficiencies based on some established performance indicators such as degree of removal of pollutants such as turbidity, colour, suspended impurities etc (Absar and Syed, 2018).
Poor drinking water quality remain one of the major threats to human health. According to the World Health Organization (WHO, 1993), 1.7 billion people are diagnosed with diarrheal diseases annually, 88% of which are attributed to unsafe water supply, inadequate sanitation and hygiene. Every one hour about 87 children under five are dying because of diarrhea (WHO; UNICEF, 2013).
Therefore, water is an important natural resource in the world, and life cannot exist and most industries could not operate without water
Для цитирования
Nahla Babiker Hussien, Abdel Moneim Osman, Mortada H.A. Elhesain, Yasir A. Mohamed. Evaluation of Water Purification Plant at Kosti City -Sudan // Вестник ВГУИТ. 2021. Т 83. № 3. С. 121-128. doi:10.20914/2310-1202-2021-3-121-128
© 2021, Nahla Babiker Hussien et al.
(Tebbutt, 1997). It is very necessary to treat water to purify water sources, make them suitable for human consumption through the removal and killing of pathogenic organisms, and remove the taste, smell, and other undesirable chemical and physical constituents (Mohammed and Shakir, 2012). In evaluation of a water treatment plant depending on treatment process efficiency, all involved processes could be assessed or a key unit is chosen to decide whether the plant operates in acceptable way or not (Wei, et al, 2010). Clean and safe drinking water is very scarce on the earth. Every day due to industrialization and uncontrolled urbanization the source of pure water are getting polluted. Cleaning the polluted water and making it safe for drinking is the main challenge in today's world (Baroniya et al, 2012).
The public health significance of water quality cannot be over emphasized. Many infectious diseases are transmitted by water through the fecal oral route. Diseases transmitted through drinking water kill about 5 million children annually and make 1/6th of the world population sick (WHO, 2004). Water used in Sudan derives almost exclusively from surface water resources, as groundwater is used in only very limited areas. Surface water is provided mainly by the River Nile (Ell-Amin etal., 2010). Water for domestic use is required to be both wholesome and safe. For health, reasons a number of chemical, physical and bacteriological quality of water are need to be considered (Tsadik, 2013).
For citation
Nahla Babiker Hussien, Abdel Moneim Osman, Mortada H.A. Elhesain, Yasir A. Mohamed. Evaluation of Water Purification Plant at Kosti City -Sudan. Vestnik VGUIT [Proceedings of VSUET]. 2021. vol. 83 no. 3. pp. 121-128.. doi:10.20914/2310-1202-2021-3-121-128 This is an open access article distributed under the terms of the Creative Commons Attribution 4.0 International License
Nakla Bafnkgr Hussien et aC Proceedings ofVSUET, 2021, vo[. 83, no.
Table 1.
Comparison between the Sudanese Standards and Metrology Organization (SSMO, 2008) and the World Health Organization (WHO, 1993) Physical and Chemical Parameters)
Physical and Chemical Parameters and Characters Sudan Permissible Maximum WHO Guide Line Value
Colour - 15 TCU
Turbidity. NTU 5.0 NTU 15.0 NTU
Odor and Taste Acceptable -
pH 6.5 - 8.5 6.5 - 8.5
TDS 1000 mg/L 1000 mg/L
Chloride 250 mg/L 250 mg/L
Sulphate 500 mg/L 400 mg/L
Fluoride 1.3 mg/L 1.5 mg/L
Hardness as Ca-C03 - 500 mg/L
Manganese 0.27mg/L 0.1 mg/L
Iron 0.3mg/L 0.3 mg/L
Sodium 250mg/L 200 mg/L
Copper 1.5 mg/L 1 mg/L
Zinc - 5 mg/L
Nitrate as N03 50 -200mg/L 50mg/L
Nitrate as N 0.03 mg/L 0.05 mg/L
Arsenic 0.03 mg/L 0.05 mg/L
Lead Ns Ns
Barium Ns 0.005 mg/L
Cadmium - 0.01 mg/L
Selenium 0.04 mg/L 0.05 mg/L
Chromium Ns 0.001 mg/L
Mercury - Ns
BOD - 5mg/L
Diedrin 0.2 mg/L 0.3 mg/L
Chlordin - -
COD - 10mg/L
Iodine - -
Calcium 0.002mg/L -
Magnesium 0.27mg/L -
Aluminum 0.13mg/L -
Residual Chlorine 0.2-0.4mg/L 0.3 - 0.5 mg/L
Electrical Conductivity Ns 1600 mi-cromohs/cm
Ns = No standard - = Not found
The problem of supplying adequate amount of safe water for distribution to the public does not end with the construction of water works recently, in Kosti city drinking and general-purpose water is supplied by the White Nile. The water of the White Nile is very turbid, therefore, it is expected to be contaminated with chemicals, as well as microorganisms and accordingly it may cause health problems such as toxicity and some diseases and disorders. Therefore, the present investigation was carried out in an attempt to study the drinking water quality in Kosti city.
3, pp. 121-128 [email protected]
Materials and Methods
Location of the Study Area
This study was carried out on drinking water samples collected from different locations at city Kosti, White Nile State. It is located on the west bank of the White Nile. Furthermore, Kosti is considered as a central point of travel and communication as it is largest river port in Sudan, which connects north of Sudan government to the south of Sudan government. In recent years Kosti has grown fast due to war and draught that affect southern and western regions of the Sudan
Process Description
Water is taken from water source (White Nile) The water is drawn from the supplier with pull pumps They have filters to prevent the entry of large materials such as wood, fish and plants.
Water is transferred to rapid mixing tanks, where the water is mixed with a hydraulic mixer powered by water in order to break the large particles attached to facilitate the deposition process the poly-aluminum chloride is added to its high efficiency in removing the suspended materials the water is then transferred from the rapid mixing basin to the settling basin where the suspended material is deposited in the bottom of the basin and disposed of by a shovel located at the bottom of the basin. The pure water is transferred to the filtration basin. The water is collected after removing it from the filters in the sterilization tanks where the chlorine is added in either the form of liquid, solid or gas, which is the most efficient, then the water is left for a period ranging from 2.5 to 4 hours and then the water is distributed to the transport networks by the pumps.
Figure 1. Schematic diagram of the Stages of Water Purification, in Kosti City
Sampling
Samples were collected from different sites along the network line of drinking water system that supply Kosti city. Five sites were selected for sampling was as followed:
Site 1: The Raw water in plant.
Site 2: The Treated water in plant.
Site 3: 27 quarter.
Site 4: El Hila El Gadida quarter.
Site 5: El Nasri quarter.
Nahla BaSiker Hussien et al. Proceedings ofVSUET, 2021, voC 83,
Sampling Techniques
Water samples were collected aseptically in sterile bottles. The opening of the tap was cleaned, sterilized by alcohol, and flaming.
The tap was then opened, first stream was discarded, and after 2 minutes, the target sample was collected in sterile bottle. The bottle was tightly closed and immediately transported to laboratory for chemical and bacteriological analysis. The chemical and bacteriological analysis was carried out in Chemistry Laboratory at University of El-imam El-Mahdi and Kosti Water Analysis Laboratory.
Materials
The materials used throughout this study include:
1. Sample of water.
2. Media Macconky Broth.
3. Media M-Endo Agar LES.
4. Media Brillint Green Bile Broth-2%.
5. Distilled Water.
6. Sulphuric Acid (H2 S04).
7. Starch Indicator.
8. Sodium Iodine (NaI).
9. Manganese Sulphate (MnS04).
10. Copper Sulphate (CuS04).
11. Potassium permanganate (KMn04).
12. Sodium Oxalate (0.025N) (Na2 C204).
13. Sodium Thiosulfate (Na2S203).
14. Ammonium Chloride (NH4 Cl).
15. Ammonium Hydroxide (NH4 OH).
16. EDTA solution.
Equipment and Devices
The apparatus used throughout this study include:
1. Turbdiymeter type2100N made in Japan.
2. Ectype 214 Conductivity Meter made in Portugal.
3. Ph-type 211 Microprocessor PH - meter made in Portugal.
4. Incubation type 06287 Akyoet made in Turkey.
5. Water Bath - Mumbai type 400013made in India.
6. Electronic Digital Balance type 0512madein China.
7. TDS/TEMP type 122 TDS Meter made in China.
8. Autoclave type H T30 psi made in Turkey.
9. Laboratory glass Equipment's, thermometer rang of (0-50°C); burette capacity (0-100 Ml); different type of cylinder (10-500 Ml); test tube; Petri dishes; different type of beakers (50-100250 mL); different type of funnels (50-100-150250-1000 ML).
10. Laboratory Consumptions (gloves -facemask - Cotton - soap).
no. 3, pp. 121-128 [email protected]
Physical Tests
Measurement of the temperature. 100 ml of water sample was taken in a beaker to measure the temperature by using thermometer device then the readings were recorded.
Test of Total Dissolved Solids (TDS(. 100 ml of water sample were taken in a beaker to measure the amount of total dissolved solids by using TDS meter device then the readings were recorded.
Test of Turbidity. Sample of water was taken in device tube turbdiymeter after calibration the device tube is empty then the readings were recorded.
Test of Electrical Conductivity (EC). 100 ml of drinking water was put in a beaker and, a conduct meter was used to measure the conductivity of water after calibration the device by buffer solution then the readings were recorded.
Chemical Tests
Measuring the degree of Ph. 100 ml of water sample was put in a beaker, Ph - meter was used to measure the Ph and then the readings were recorded.
Residual Chlorine Test. 10 ml of water sample was put in the comparison scale and then put the diethyl phenylnediamine (DPD) and dissolved in the water in the comparison scale and then the readings were recorded by comparing with the color closest to it.
Total Hardness. 1ml ammonia buffer solution and about 30mg of eriochrome black T indicator was added to 50ml water sample in 250ml conical flask .the solution was then titrated with the 0.01MEDTA solution until the color changes from wine red to blue end point and then the readings were recorded.
Hardness CaCo3mg/L = ( 4*B*100 \
' "Wl I nf c/rmn/o''
ml of sample
where A - ml of EDTA required for titration; B - mgs of CaCo3 equivalent to 1mole EDTA.
Determination the Chemical Oxygen Demand (C.O.D). 10ml of the sample were taken in 100ml bottle then 5ml of concentrate H2S04 wasadded and about 1gm of copper sulphate (CuSO4) also added. Then 3ml of prepared (0.025N) KMn04 solution was added and immersed in boiling water for 30 minutes while keeping the surface of boiling water at higher level than the surface of the sample. Three moles (3ml) were then prepared (0.025N) of sodium oxalate Na2 C2 04was added and immediately titrated with (0.025N) potassium permanganate (KMn04) until the violet colour was appeared. The experiment repeated for the blank separately under the same condition using 10 ml of distilled water instead of 10 ml of sample.
(1)
Nakla BafnkerHussien et aC Proceedings of VSUET, 2021, voC 83, no.
_sample of ml B*A*8000*0.025
COD as mg/L=
ML OF SAMPLE
(2)
where A - ml of KMn04 used sample; B - ml of
KMn04 used blank; 0.025 - Normality of
KMn04; 8000 - ml equivalent weight of oxygen in 1000 ml/L.
Determination of Biological Oxygen Demand (B.O.D). Twenty five mls sample was taken in each bottle and 75 mls of the sample was added to each of bottles then the bottles closed well .one bottle was kept in the in Cuba for at (20-22° C ) for 5 days. then 10 mls of manganese sulphate solution and 2mls of alkali - 10 ml (NaI) solution was added to the of bottle below the surface of the liquid by using a syringe .then the bottle were closed and mixed by inverting it several times when the precipitate settles leaving a clear supernatant above the precipitate, shaken again slowly by inverting the bottle and when the setting has produced at least 50mls superhot at 8 mls of conc H2 S04was added. Then the bottle was closed and mixed by gentle in version until dissolution was completed. One - hand red mls of the sample was titrated in the 0.025M Na2S203 solution until a pale yellow solution was reached. Then 2mls of freshly preparer starch solution was added and titration was continued until a blue colour appeared. the proceed me was then repeated using 100mls distilled water (blank) then, repeated for in au bated sample for 5 days and then the readings was recorded.
BOD as Mg/L = 16(VrV2) (3)
(Garcia and Stamatis, 2013) where Vi - ml of Na2 S2 03 used for the sample before incubation; V2 - ml of Na2 S2 03 used for the sample after incubation.
Microbial Load Determination
Detection of total coliform bacteria. 7.3 gm of Media Macconky Broth was added to 100 ml of distilled water the mixture was heated in Bunsen burner and then put in the autoclave for 20 minutes, then leave until cooled and then add 100 ml of the sample water and entered the incubator in the temperature of 37 ° C for 24 hours change color From darkviolet to yellow proof positive of the existence of total coliform bacteria.
Detection of Fecal Coliform Bacteria. Prepare the media Brillint Green Bile Broth-2% in the same way, bring the media in the same way with the replacement of the weight of the media by 8 grams the former and placed on tubes containing the Graham tube and add 1 ml of positive sample in the test of coliform and enter in the incubator at a temperature of 45° C for a period of 24 hours occurrence of turbidity in the color with gas surges in the Graham tube evidence of the presence of Fecal Coliform Bacteria.
3, pp. 121-128 [email protected]
Detection of Escherichia coli E. Coli Bacteria. Prepare the media M-Endo Agar LES in the same way before with the replacement of the weight of the media by 5.2 grams and then placed on the Petri dishes then was sprinkled with a positive sample of the Fecal Coliform bacteria test and placed in the incubator for 24 hours in the reference temperature 37 note gold colonies are bright in the positive samples evidence of existence E.coli bacteria.
Results and Discussions
Table 2.
The pH of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
Date Raw water Treated Water A B C
1/3/2017 7.6 7.6 7.3 7.2 7.2
15/3/2017 6.8 6.9 6.5 6.3 6.3
29/3/2017 7.8 7.8 7.8 7.6 7.4
1/5/2017 8.2 8.2 8.2 8.2 8.2
15/5/2017 7.8 7.8 7.5 7.3 7.2
29/5/2017 7.8 7.8 7.4 7.3 7.2
A: 27 Squarer - B : El Hila Elgadida - C: El Nasri Squarer
It was noticed from the Table 2 that the pH values are almost constant, the highest pH was found in May (8.2) on the 1/5/2017, while March had the lowest pH value (6.3) on the 15/3/2017 in B and C respectively.
We note that the pH values are almost constant the same for the Nile water, with a slight difference due to the quality of the water and Materials suspended with water and distribution lines of the network.
The change in pH i.e. in May (8.2) and in March (6.3) may be due to improper water treatment on that day and i.e present of same Alkalinity and acidic materiel for May and March respectively.
The high pH in the first of May was attributed to some rain fall in this period. This rain fall increase the Alkalinity of water due to some alkaline substance dissolved by the rain and PH increase in Alkalinity direction.
This result was in agreement with (Reda, 2016) finding, in her study Physicochemical Analysis of Drinking Water Quality of Arbaminch Town. She found that the values of Ph were 7.5, 7.1, 7.7. We find pH values that falls within the permissible limit (6.5-8.5).
Table 3.
The Electrical conductivity (^s/cm) of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
Date Raw water Treated water A B C
1/3/2017 160 158 162 156 174
15/3/2017 140 128 122 116 154
29/3/2017 144 130 135 130 144
1/5/2017 214 213 216 210 224
15/5/2017 224 223 226 220 234
29/5/2017 220 219 222 216 224
Nahla BaSiker Hussien et aC Proceedings ofVSUET, 20)21, vo. 83,
The results obtained showed that the conductivity varied among months for all locations with the highest value (234 ^s/cm) obtained during May at station (C) 15/5/2017 and the lowest value (116^s/cm) obtained during March at station (B) 15/3/2017. These results show that electrical conductivity increases near the autumn season and decreases in the summer. The different in conductivity between Raw and Treated Water may be attributed to the fact that when raw water was treated some materials were removed and this cause the low thermal conductivity in Treated Water.
The turbidity level (NTU) and removal rate%of Kosti w
period March 20
Pipe line were very old at some areas or places so some materials like mineral may enter in the pipe line due to some breakage or some openings.
This result was in agreement with (Abdel-magid et all, 1984) finding, in his study Chemical and Microbiological examination of well and Nile water. he found that the values of electrical conductivity were 150,170, 305^s/cm. All the reading fall below the acceptable level of WHO and, Sudanese Standards and Metrology Organization (1600 ^s/cm).
Table 4.
ater network distribution pipeline at five sites during the 17 and May 2017
Date Raw water Treated water A B C Removal rate % Raw and treated water Removal rate % Raw and A Removal rate % Raw and B Removal rate % Raw and C
01/3/2017 6.3 6.2 4.2 4.4 5 1.6 58.3 30.2 20.6
15/3/2017 7.4 6.5 4.6 4.9 5.2 12.2 37.8 33.8 29.7
29/3/2017 12.1 8.4 4.8. 5 6.1 30.6 60.3 58.7 49.6
01/5/2017 120 64 35.2 49.3 50 46.7 70.7 58.9 58.3
15/5/2017 143 84.4 45.1 48.2 61 50 68.5 66.3 57.3
29/5/2017 150 94.5 55.5 58.3 60 37 63 61.1 60
Removal rate%=
_ i n s i d e tu r b i d ity - o u ts i d e tu r b i d i ty.
*100%
(4)
inside turbidity
Table 4 show the highest value of turbidity (150 NTU) was reported in site raw water while the lowest value (4.2 NTU) was reported in site A. The White Nile becomes very narrow in summer and this causes difficulty in water pumping, which in turn contaminate the pumped water with solids and soil particles. Generally the turbidity was increased and stagnate in the month of May towards June and August and these month are Autumn months and as we know the turbidity of these month is very high. We find the percentages of water turbidity removed% are different, not fixed. And the maximum removal rate occurred on the 1/5/2017 amounted to 70.7%. And the lowest removal rate occurred onthe 1/3/2017 and reached.
This result was in agreement with (Siddig, 2007) finding, in her study Assessment of Drinking.
Water Quality of Kosti City. She found that the values of turbidity were 40, 70, 75 NTU. The turbidity values of Kosti water exceed the permissible level of WHO and Sudanese Organization for Standardization and Metrology (5 NTU).
Table 5.
The residual chlorine level (mg/L) of Kosti water network distribution pipeline at four sites during the period March 2017 and May 2017
Date Treated water A B C
01/3/2017 0.3 0.2 0.2 0.2
15/3/2017 0.2 0.2 0.2 0.2
29/3/2017 0.4 0.4 0.4 0.4
01/5/2017 0.2 0.2 0.2 0.2
15/5/2017 0.2 0.1 0.1 0.1
29/5/2017 0.2 0.1 0.1 0.1
As observed in Table 5 there is a fluctuation in the residual chlorine sometime decreases and sometime remains in the same level this was attributed to presence of some microorganisms needed for sterilization. This result was in agreement with (Siddig, 2007) finding, in her study Assessment of Drinking Water Quality of Kosti City. She found that the values of residual chlorine were 0.2, 0.4, 0.5 mg/L. The residual chloride between (0.1-0.4) mg/L, which means it falls minim of the permissible limits.
Table 6.
The total dissolved solids (TDS) (mg/L) of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
Date Raw water Treated water A B C
01/3/2017 111 111 115 114 112
15/3/2017 120 122 120 122 123
29/3/2017 123 122 124 123 120
01/5/2017 130 130 129 128 129
15/5/2017 140 141 140 138 142
29/5/2017 156 157 160 155 152
From Table (6) the highest value (157mg/L) was reported in May while the lowest one (111mg/L) was reported in March. There is no significant difference in total dissolved solids between raw water and treated water and distributed water at station A, B, C this means that all the dissolved substance and minerals in water more or less is it not reduced nor increased.
This result was in agreement with (Siddig, 2007) finding, in her study Assessment of Drinking Water Quality of Kosti City. She found that the values of total dissolved solids were 80, 101, 130 mg/L .All the readings fall below the value of the WHO standards (1000 mg/L).
Table 7.
Chemical oxygen demand (C.O.D) (mg/L) of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
Date Raw Treated A B C
water water
01/3/2017 154.8 129 120.4 111.8 86
15/3/2017 240.8 215 206.4 197.8 94.6
29/3/2017 326.8 301 301 283.8 103.2
01/5/2017 412.8 387 378.5 369.8 120.4
15/5/2017 498.8 473 464.4 455.5 206.5
29/5/2017 584.8 559 550.4 541.8 292.5
Table 9.
Caption
Date Raw water Treated water A B C
01/3/2017 + - - - -
15/3/2017 + - - - -
29/3/2017 + - + - -
01/5/2017 + - - - +
15/5/2017 + + + + +
29/5/2017 + + + + +
+ The presence of bacteria in the sample; - There are no bacteria in the sample
From Table (7) the highest value of COD (584.8mg/L) was reported in site raw water, while the lowest one (86 mg/L) was reported in site C. The highest value of COD in raw water was attributed to high turbidity of water and contamination which may include some of organic matter that need more COD to be converted to inorganic matter.
This result was in agreement with (Sharma and Gupta, 2013) finding, in his Study of amount of Oxygen (BOD, OD, COD) in water and their effect on fishes he found that the values of chemical oxygen demand were12.2, 34.2, 12.9 mg/L. The COD values of Kosti water exceed the permissible level of WHO standards (10 mg/L).
Table 8.
Biological Oxygen Demand (B.O.D) (mg/L) of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
From Table (8) the highest value of BOD (144 mg/L) was reported in site raw water, while the lowest one (16 mg/L) was reported on 29/5/2017 in station A. The highest value of BOD was reported in raw water this is an indicator for the presence of microorganisms in water and microorganisms need oxygen.
This result was in agreement with (Sharma and Gupta, 2013) finding, in his Study of amount of Oxygen (BOD, OD, COD) in water and their effect on fishes he found that the values of Biological oxygen demand were 5.2, 8. 3,3.2 mg/L. The BOD values of Kosti water exceed the permissible level of WHO standards. (5mg/L).
Total coliform Bacteria per 100 ml of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017.
From Table (9) there is presence of microorganisms in treated water on the days 15/5/2017 and 29/5/2017 in station A, B, C this means that the treatment of water was not sufficient and consequently there was presence of positive signal (+) which means the presence of Total coliform Bacteria. This result was in agreement with (B. et all. 2008) finding, in his Study Physico Chemical and Bacteriological Analyses of Water Used for Drinking and Swimming Purposes in Abeokuta, Nigeria. The Contents of Microorganisms According to Sudanese Specifications and Sudanese Organization for Standardization and Metrology 2008 recommended that the permissible Total col-iform Bacteria count be around 0.0.
Table 10.
Fecal Coliform Bacteria per 100 ml of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
From Table (10) there is presence of microorganisms in treated water on the days 15/5/2017 and 29/5/2017 in station A, B, C this means that the treatment of water was not sufficient and consequently there was presence of positive signal (+) which means the presence of Fecal Coliform Bacteria. This result was in agreement with (B. et all., 2008) finding, in his Study
Physico Chemical and Bacteriological Analyses of Water Used for Drinking and Swimming Purposes in Abeokuta, Nigeria.
The Contents of Microorganisms According to Sudanese Standards and Metrology Organization (2008) recommended that the permissible Fecal Coliform Bacteria count be around 0.0.
Date Raw water Treated water A B C
01/3/2017 54.5 36 17 16 32
15/3/2017 136 96 64 19.5 16
29/3/2017 144 104 72 32 17
01/5/2017 128 35.5 48 35.2 32
15/5/2017 112 36 32 36.2 17
29/5/2017 96 70.5 16 17 33
Date Raw water Treated water A B C
1/3/2017 + - - - -
15/3/2017 + - - - -
29/3/2017 + - - + -
1/5/2017 + - - - +
15/5/2017 + + + + +
29/5/2017 + + + + +
+ The presence of bacteria in the sample; - There are no bacteria in the sample
Table 11.
Escherichia coli (E. coli) per 100 ml of Kosti water network distribution pipeline at five sites during the period March 2017 and May 2017
Date Raw water Treated water A B C
1/3/2017 + - - - -
15/3/2017 + - - - -
29/3/2017 + - - + -
1/5/2017 + - - - +
15/5/2017 + + + + +
29/5/2017 + + + + +
+ The presence of bacteria in the sample; - There are no bacteria in the sample
This result was in agreement with (B. et all, 2008) finding, in his Study Physico Chemical and Bacteriological Analyses of Water Used for Drinking and Swimming Purposes in Abeokuta, Nigeria.
The Contents of Microorganisms According to Sudanese Organization for Standardization and Metrology (2008) recommended that the permissible Escherichia coli Bacteria count be around 0.0.
The overall results there were presence of Total coliform Bacteria, Fecal Coliform Bacteria and Escherichia coli all Microorganisms on their days (15/5 and 29/5/2017) this is strong evidence for the contamination on these periods.
From Table (11) there is presence of microorganisms in treated water on the days 15/5/2017 and 29/5/2017 in station A, B, C this means that the treatment of water was not sufficient and consequently there was presence of positive signal (+) which means the presence of Escherichia coli.
References
Conclusion
The quality of Kosti city drinking water under the study was found to be in the required range according to Sudanese Standards and Metrology Organization (2008) and World Health Organization (WHO, 1993).
1 Niu J., Kasuga I., Kurisu F., Furumai H. et al. Evaluation of autotrophic growth of ammonia-oxidizers associated with granular activated carbon used for drinking water purification by DNA-stable isotope probing. Water research. 2013. vol. 47. no. 19. pp. 7053-7065. doi: 10.1016/j.watres.2013.07.056
2 Khan A.A., Ahmad S.K. Performance evaluation of water treatment plant at nangloi. New Delhi: a case study ijret: International Journal of Research in Engineering and Technology. 2018.
3 Al-Jlil S.A., Alromaih H., Alshabonah F., Alsoubaei F. et al. Evaluation of Performance of Wastewater Treatment Plant at KACST, Riyadh Saudi Arabia. Research Journal of Environmental Sciences. 2014. vol. 8. no. 2. pp. 117-122.
4 Shittu B.O., Olaitan O.J., Amusa S.T. Physico-Chemical and Bacteriological Analyses of Water Used for Drinking and Swimming Purposes in Abeokuta, Nigeria. African Journal of Biomedical Research. 2008. vol. 11.
5 Mamta B., Singh B. S., Monica J. Operation and maintenance of water treatment plant at BNP Campus Dewas, India: A case study. ISCA Journal of Biological Sciences. 2012. vol. 1. no. 1. pp. 83-86.
6 Ell-Amin A.M., Sulieman A.M.E., El-Khalifa E.A. Quality characteristics of drinking water in Khartoum state and Wad-Medani District, Sudan. 14th international water technology conference, IWTC. 2010. vol. 14. no. 2010. pp. 863-876.
7 Verma N., Singh A.K. Development of biological oxygen demand biosensor for monitoring the fermentation industry effluent. International Scholarly Research Notices. 2013. vol. 2013. doi: 10.5402/2013/236062
8 Mohammed A.A., Shakir A.A. Evaluation the performance of Al-wahdaa project drinking water treatment plant: A case study in Iraq. International Journal of Advances in Applied Sciences. 2012. vol. 1. no. 3. pp. 130-138.
9 Reda A.H. Physico-chemical analysis of drinking water quality of Arbaminch Town. J Environ Anal Toxicol. 2016. vol. 6. no. 2. pp. 1-5.
10 Sharma P., Gupta S. Study of amount of Oxygen (BOD, OD, COD) in water and their effect on fishes. American International Journal of Research in Formal, Applied and Natural Sciences. 2014. vol. 7. no. 1. pp. 53-58.
11 Somani S., Ingole N., Patil S. Performance evaluation of natural herbs for antibacterial activity in water purification. International Journal of Engineering Science and Technology. 2011. vol. 3. no. 9. pp. 7170-7174.
12 SSMO, (2008) Sudanese Standards and Metrology Organization.
13 Kpan W.B., Kone M.W., Bonfoh B., Kamanzi K. Evaluation of eighteen west african plants for water purification, potential use for rural water treatment. Journal of Water Chemistry and Technology. 2017. vol. 39. no. 5. pp. 310-316. doi: 10.3103/S1063455X17050101
14 Tsadik T.G Performance Evaluation of Drinking Water Gambella Town Drinking Water Treatment Plant. School of Graduate Studies of Addis Ababa University fulfillment of the Degree of Chemical Engineering M.S.c. Science in Environmental Engineering. 2013.
15 Wei J., Ye B., Wang W., Yang L. et al. Spatial and temporal evaluations of disinfection by-products in drinking water distribution systems in Beijing, China. Science of the Total Environment. 2010. vol. 408. no. 20. pp. 4600-4606. doi: 10.1016/j.scitotenv.2010.06.053
16 WHO. Water Sanitation and Health Programmed. Managing water in The home: accelerated health gains from improved water sources. World Health Organization. 2004. Available at: www.who.int
17 WHO. UNICEF. WHO / UNICEF Joint Monitoring Programme (JMP) for Water Supply and Sanitation. Retrieved December 11, 2013. Available at: http://www.wssinfo.org/definitions methods/introduction/
18 Jordanowska J., Jakubus M. Evaluation of effectiveness technological process of water purification exemplified on modernized water treatment plant at Otoczna. Civil and Environmental Engineering Reports. 2014. doi: 10.2478/ceer-2014-0014
19 Verma S.K., Singhal P., Chauhan D.S. A synergistic evaluation on application of solar-thermal energy in water purification: Current scenario and future prospects. Energy conversion and Management. 2019. vol. 180. pp. 372-390. doi: 10.1016/j.enconman.2018.10.090
20 Elasaad H., Bilton A., Kelley L., Duayhe O. et al. Field evaluation of a community scale solar powered water purification technology: A case study of a remote Mexican community application. Desalination. 2015. vol. 375. pp. 71-80. doi: 10.1016/j.desal.2015.08.001
Information about authors
Nahla Babiker Hussien lecturer, food processing engineering department, Faculty of Engineering and Technical Studies, University of El Imam El Mahdi, Kosti, P. O. box 209 Sudan, [email protected]
Abdel Moneim Osman A. Babikr Dr. associate professor, food processing engineering department, Faculty of Engineering and Technical Studies, University of El Imam El Mahdi, Kosti, P. O. box 209 Sudan, [email protected] Mortada H.A. Elhesain Dr., associate professor, food processing engineering department, Faculty of Engineering, University of El Imam El Mahdi, Kosti, P. O. box 209 Sudan, [email protected]
Yasir A. Mohamed Dr. professor, chemical engineering department, Faculty of Engineering & Technical Studies, University of El Imam El Mahdi, Kosti, P. O. box 209 Sudan, [email protected]
Contribution
Nahla Babiker Hussien corrected the manuscript, improved the results discussion and put in the format required by the Journal before filing in editing.
Abdel Moneim Osman A. Babikr review of the literature on the investigated problem, conducted the experiments, performed the characterizations and measurements, and wrote the manuscript
Mortada H.A. Elhesain corrected the manuscript, improved the results discussion and put in the format required by the Journal before filing in editing and is responsible for plagiarism.
Yasir A. Mohamed proposed a scheme of the experiments and organized production trials, corrected the manuscript, improved the results discussion and put in the format required by the Journal before filing in editing and is responsible for plagiarism