COUNTERMEASURE FOR MINIMIZE UNWANTED ALARM OF AUTOMATIC FIRE NOTIFICATION SYSTEM IN THE REPUBLIC OF KOREA
Kong, Hasung 1
1 Kyungil University, Republic of Korea
50, GAMASIL-GIL, HAYANG-EUP, GYEONGSAN-SI, GYEONGBUK, 712-701 KOREA
Associate professor, Academic degree and academic rank: Master of Engineering E-mail: komgus@mail.ru
Received: 04/10/2015 Approved: 05/15/2015
Abstract
In this article investigated the cause of error through survey to building officials for minimizing the unwanted alarm of automatic fire notification and suggested countermeasure for minimizing the unwanted alarm. The main cause of the unwanted alarm is defective fire detector, interlocking with automatic fire detection system, lack in fire safety warden's ability, worn-out fire detect receiving system. The countermeasure for minimizing unwanted alarm is firstly, tightening up the standard of model approval, Secondly, interlocking with cross-section circuit method fire extinguishing system or realizing automatic fire notification system interlocking with home network, thirdly, tightening up licensing examination of fire safety warden, lastly, it suggested term of use rule of fire detect receiving system.
Keywords: automatic fire notification system, automatic fire detection system, cross-section circuit method, home network, fire safety warden. Correspondence: Kong, Hasung, Kyungil University, Republic of Korea (50, GAMASIL-GIL, HAYANG-EUP, GYEONGSAN-SI, GYEONGBUK, 712-701 KOREA), komgus@mail.ru
Reference: Kong Hasung. Countermeasure for Minimize Unwanted Alarm of Automatic Fire Notification System in the Republic of Korea. M.I.R. (Modernization. Innovation. Research), 2015, vol. 6, no. 2, part2, pp. 23-25.
In this article investigated not only cause of the errors via an analysis of frequency from Dec. 1st,. 2014 to Dec. 30th., 2014 against total 400 firefighters such as 200 firefighters in the Seoul metropolitan city and the local metropolitan city, and also 200 firefighters in each province by carrying out the questionnaires for the person concerned with building that the automatic fire notification system has been installed in order to minimize some malfunctions of the automatic fire notification system, but also this study has suggested it's countermeasures for the sake of some malfunctions of the automatic fire notification system.
1. The analysis of the questionnaires against the person concerned with the automatic fire notification system.
Table 1
The results of the questionnaires
Questionnaires Headcount Percent* go <%)
1, Have malfunction instances of automatic fire notification system in building existed or not? I0U
Malfunction instances have existed. 232 58
© Malfunction instances one have never existed, m 42
2. If malfunction instances have existed have how many times of malfunction occurred yearly? •100 100
Onee-twlcc 192 48
©Tliricc-4"\ ЯН 22
@ 5* - n 6U'. 52 13
ffi 7* Ovur 68 17
Table continuation 1
3, When you activate the automatic fire notification system., What should we do? 400 100
First of all, keep an eye on whether fire breaks. 348 87
First of al 1r we should report to a fire station. 28 7
We should interrupt a power source of the automatic fire delect receiving system, 16 4
We should receive help from neighborhood resident*. 8 •>
4, In case that malfunction of die automatic tire detect receiving system Wilh confirmed, w hat is the measures that wc should lake? 400 100
Wc should interrupt to supply power source of the automatic fire detect receiving system. 24 6
© Wc should restore to the original state by a self-inspection. 25b 64
© We should receive help from firefighters by reporting some fire occurrence to a regional tire station, 24 6
We should lake a proper теакиге* by keep in touch with The fire fighting facilities management enterprise. 96 24
5, In case that the automatic tire delect receiving sysicm is operated, whul idea conies to mind first? 400 100
And also malfunction of the automatic tire delect receiving System was generated, because someone touched With hands. 88 22
The unbelievable automatic fire delects receiving, system. 20 5
How <to wc tranquillize some astounded persons? 204 51
Wc should do alternate it with a new product, 88 yi
6. What do you think of main causes of malfunction uf the automatic fire delect receiving system? 400 100
On account of Hie aged deterioration of the automatic fire detect receiving system, malfunction is occurred. 180 45
@ A tire safety warden U likely not to manage ihe fire protection sysicm well. 56 14
(D Malfunction of the automatic Eire detect receiving system is also attributable to a low-priced product. 56 14
The reason is attributable to a shoddy and fault construction of a certain fire protection facilities construction company. 60 15
ttcclcra, 48 12
7. What are indispensable particulars for the purpose of malfunctioning prevention of the (ire detect receiving system? 400 100
Performance improvement of the fire protection system. 128 32
23
МИР (Модернизация. Инновации. Развитие). 2015. Т. 6. № 2. Часть 2. С. 23-26
End table 1
Professional education (hat is aimed at the parties concerned. 96 24
Л shoddy and fault prevention of the fire protection system. 4Я 12
Thorough management of a certain Are protection facilities management company. 84 23
Introduction иГ the aged deterioration system fur the product. 44 tl
What is your frank opinion about the automatic tire notification system? 400 100
Wo think that the automatic (ire notification System is not necessary. 12 3
The automatic fire notification system is indispensable. 304 76
We think dial the automatic fire notification system should be mitnaged and controlled, should be included in Hume network. 72 IS
We think that the automatic Eire notification system is wasteful. t2 3
Data report: Extracted from Cheon II Ryeon etc. (2014)
2. Countermeasures to minimize malfunction of automatic fire detect receiving system.
Malfunction cause and countermeasures to minimize malfunction that is based on questionnaires aimed at the persons concerned in building that the fire detect receiving system was installed is as follows:
2.1. Criteria reinforcement for type approval of the fire detector.
In case that the fire detect receiving system functions, notwithstanding that a fire safety warden should take a measure for the sake of the fire extinguishing, notification, evacuation, the persons who keep an eye out immediately whether fire actually occurred first of all occupied not only 78%, but also occurrence of malfunction occupied 22% because someone handled the fire detect receiving system, and the persons who should take the tranquilizing measures occupied 51%. These facts are grasped as phenomena that are appeared by increasing of malfunction rates of the automatic fire detect receiving system owing to the faulty sensor that receives the signal fire. It is necessary to prepare how to decrease malfunction
rates by improving the high quality of the fire sensor, strengthening the type approval standard of the fire sensor as a complementary countermeasure.
2.2. Interlocking with gas type fire extinguishing system of cross-section circuit method.
The automatic fire notification system can decrease malfunction due to the fire sensors via system improvement to be interlocked with the existing automatic fire detection system. Whenever only a fire sensor is functioned, in case that only one sensor function, after the sensor circuit method is interlocked with the fire protection system such as the automatic fire detection system and preaction sprinkler system, gas type fire extinguishing system, when more than 2 sensor circuit was functioned, it is necessary to decrease malfunction that is occurred because of the fire sensor by telecommunicating fire signal to the automatic fire detect receiving system after altering to the method that telecommunicate fire signal[4].
Table 2 2.3. Embodiment of the automatic fire
notification system that was interlocked with home network.
Opinions that performance of the fire protection system should be improved in order to prevent malfunction of the automatic fire notification system was the most as 32%. Because the existing automatic fire notification system is functioned by receiving fire signals from the automatic fire detection system, it is difficult to secure reliability for fire[5]. In a questionnaire survey, just like 18% of respondents respond that should be included to home network. The existing automatic fire detection system is necessary to judge accurately whether actual fire was occurred or not, interlocking with the video camera
images as a security system in order to receive the fire warning signal via heat sensors and smoke sensors of the existing automatic fire detection system [6].
2.4. The qualifying examination strengthening of the fire safety warden.
In case to be confirmed that the automatic fire notification system was malfunctioned, ratio to be restored according to self investigation and the way how the concerned persons handled the situation is the most as 64%, and ratio that measures are taken contacting to fire-fighting facilities management company was investigated as 24%, but the meaning of self-investigation mean level degree that block out power source of the automatic fire notification system, and capability that can grasp it's cause and cope with itself seems to be insufficient[7]. Fire safety
Malfunction cause and the countermeasures to minimize malfunction of the automatic fire notification system
Malfunction cause Countermeasures to minimize malfunction
Defects of fire sensors. Criteria reinforcement for type approval Of the fire sensors.
Interlocking with the automatic fire detection system. Interlocking with the fire extinguishing system of cross-section circuit method.
Embodiment of the automatic fire detects receiving system that was interlocked with home network.
Ability shortage of fire safety warden. Strengthening of a qualifying examination for a fire safety warden.
Deterioration of the automatic fire detects receiving system. Regulation of Service life for the fire detects receiving system.
Data report: to be arranged on the basis of a questionnaire survey that is aimed at the persons concerned in building
24
M.I.R. (Modernization. Innovation. Research), 2015, vol. 6, no. 2, part 2, pp. 23-26
warden operate the automatic fire notification system and should carry out jobs such as composition of the initial response system, operation and management, education, evacuation shelter's facilities, fire compartment and maintenance management of fire-prevention system, but job performance of fire safety warden is grasped to be low[8]. And also opinions that professional education for the concerned persons in order to prevent malfunction of the automatic fire notification system is necessary occupy a large numbers as 24%. Therefore it is necessary to strengthen theory-centered education, decision of the success or failure from a written examination, fire notification, problems for shortage of evacuation course, practical service centered education, alteration from assessing methods to theory and practical training, fire notification and evacuation course as educational course[9].
2.5. Regulations on a service life of the automatic fire notification system.
Opinions that main cause of malfunction of the automatic fire notification system is occurred on account of deterioration of facilities are the most as 45%. In case of the current automatic fire notification system, once the current automatic fire notification system is installed, unless someone build a new building, and also before the building demolition, because the cases that the automatic fire notification system continue to be maintained are plenty of, the cases that be reluctant to alternate on account of cognition as so-called unnecessary facilities and consumption of high cost, although alternation is necessary is occurred [10]. Therefore regulating a service life enough to be criteria of the automatic fire notification system, the deteriorated automatic fire notification system is necessary to enforce by defining by law so that the regular alternations for the automatic fire notification system may are achieved. In conclusion, as a countermeasure for minimization of malfunction, firstly, reinforcement of the type approval standard for the sake of quality improvement of fire sensors, secondly, instead of interlocking method with the automatic fire detection system, interlocking with gas type fire extinguishing system of the cross-section circuit method or embodiment of the automatic fire notification system to be interlocked with home network, thirdly improvement reinforcement of a qualifying examination for fire safety warden, fourth, regulation on service life of the automatic fire notification system for the sake of alternation of the old facilities and so on are necessary.
References
1. Son Young Jin, Lee Young Il, Lee Sang Hyeon (2008). "Research on the Reliability Improvement of Automatic Fire Alarm System". Journal of Korean Institute of Fire Science & Engineering, Vol.22, No.4, 43.
2. Lee Jong Hwa, Lee Chun Ha, Kim Shi Kuk, Kong Hasung(2011). "A Study about False Alarm of Automatic Fire Detection System". Journal of Korea Safety Management & Science, Vol. 13, No.1,42.
3. Kim Tae Don (2005). "A Study on the Improvement of False Fire Alarm in Auto Fire Detect System". University of Seoul Master’s Thesis, 28-30.
4. Kong Hasung etc. (2012). Engineering of Fire Alarm Systems. Daegu: Yesmedia, 3-22.
5. Cheon Il Ryeon etc. (2014). "The Study on
Unwanted Alarm and Countermeasure of Fire Detect Receiving System of Automatic
Fire Notification System". Human Resources Development Service of Korea Research Reports,
5.
6. Cheon Il Ryeon etc. (2014). "The Study on
Unwanted Alarm and Countermeasure of Fire Detect Receiving System of Automatic
Fire Notification System". Human Resources Development Service of Korea Research Reports, 87-91.
7. Choi Yeong Gi (2014). "A Study on Fire Safety Management Status Analysis Countermeasures of Medium and Small-Sized the Manufacturing Plants". Korea National University of Transportation Master’s Thesis, 35.
8. Ministry of government legislation of Korea (2015). "Act on Installation, Maintenance and Safety of Fire Protection System" Article 20 paragraph
6. Seoul: Ministry of government legislation of Korea, 9.
9. Lee Sang Pal, Bae Jae Hyeon (2013). "Study on the Analysis and Development of the Fire Safety Director System". Korea of Public Administration, 63-88.
10. Kim Tae Don (2005). "A Study on the Improvement of False Fire Alarm in Auto Fire Detect System". University of Seoul Master’s Thesis, 24.
25
МИР (Модернизация. Инновации. Развитие). 2015. Т. 6. № 2. Часть 2. С. 23-26
МИР (Модернизация. Инновации. Развитие) МОДЕРНИЗАЦИЯ
ISSN 2411-796X (Online)
ISSN 2079-4665 (Print)
СОВРЕМЕННЫЕ МЕРЫ ПО МИНИМИЗАЦИИ ЛОЖНЫХ СРАБАТЫВАНИЙ ОБОРУДОВАНИЯ АВТОМАТИЧЕСКОЙ ПОЖАРНОЙ СИГНАЛИЗАЦИИ В КОРЕЕ
Гон Хасон
Аннотация
В настоящем исследовании в целях минимизации ложных срабатываний оборудования автоматической пожарной сигнализации в результате проведения опроса среди управляющих зданиями и частотного анализа определяются причины ошибок и предлагаются меры по минимизации ложных срабатываний. Основными причинами ложных срабатываний являются брак в пожарных датчиках, синхронизация с автоматическими системами обнаружения пожара, недостаточность навыков ответственных за пожарную безопасность, старение автоматических пожарных извещателей и т.п. В качестве мер по минимизации ложных срабатываний предлагаются, во-первых, ужесточение нормативов утверждения моделей пожарных датчиков, во-вторых, синхронизация с системами пожаротушения по методу перекрестного замыкания или реализация оборудования автоматической пожарной сигнализации, синхронизированного с домашней сетью, в-третьих, ужесточение квалификационных экзаменов для ответственных за пожарную безопасность, в-четвертых, определение сроков использования автоматических пожарных извещателей Ключевые слова: автоматическое устройство по оповещению при пожаре; устройство автоматического определения; метод перекрестного замыкания; домашняя сеть; ответственный за пожарную безопасность.
Для корреспонденции: Kong, Hasung, Kyungil University, Republic of Korea (50, GAMASIL-GIL, HAYANG-EUP, GYEONGSAN-SI, GYEONGBUK, 712-701 KOREA), komgus@mail.ru
Для ссылки: Гон Хасон. Современные меры по минимизации ложных срабатываний оборудования автоматической пожарной сигнализации в Корее//МИР (Модернизация. Инновации. Развитие). 2015.Т. 6. № 2. Часть 2. С. 23-26.
Научно-практический журнал
МИР (Модернизация. Инновации. Развитие)
приглашает к сотрудничеству новых авторов Основные требования к статьям:
1. Статья представляется в электронном виде в форматах .doc и .rtf и в виде распечатки.
Статья на бумажном носителе должна строго соответствовать рукописи но электронном носителе.
Все аббревиатуры следует расшифровывать. Возможно предоставление научной статьи и сопроводительного письма по электронной почте.
2. Распечатка научной статьи должна быть подписана автором с указанием даты ее отправки.
3. Объем научной статьи должен быть не менее 10 и не более 25 страниц, напечатанных через 1,5 интервала с размером шрифта не менее 14. Рекомендуемый тип шрифта - Times New Roman,
4. К кождой статье необходимы ФИО автора, нозвание статьи, аннотация и ключевые слова на русском и английском языках,
5. Авторам статей, утвержденных к публикации Научно-редакционным советом, в обязательном порядке необходимо заполнить анкету автора и выслать на электронный адрес журнала свою фотографию в графическом формате (.jpg, .tif}.
6. Оформление библиографического списка, обязательного в конце статьи, должно соответствовать ГОСТ Р 7.0.5-2008.
Научно-редакционный совет оставляет за собой право на редактирование статей. Статьи, не соответствующие указанным требованиям, не публикуются и не возвращаются авторам.
Статьи и все материалы к ним ждем по адресу: info@idnayka.ru
26