Научная статья на тему 'FERRORESONANCE IN ELECTRICAL NETWORK 6-35 kV'

FERRORESONANCE IN ELECTRICAL NETWORK 6-35 kV Текст научной статьи по специальности «Электротехника, электронная техника, информационные технологии»

CC BY
2
1
i Надоели баннеры? Вы всегда можете отключить рекламу.
Ключевые слова
6-35kV electrical network / ferroresonance / power voltage transformer / nonlinear inductance / dynamic model / equivalent parameters / Weber-Ampere characteristic / boundary conditions of ferroresonance stability

Аннотация научной статьи по электротехнике, электронной технике, информационным технологиям, автор научной работы — Sh. Begmatov

Ferroresonance in 6-35kV electrical networks and the cause of power voltage transformer damage are considered. To study ferroresonance, a reliable dynamic model of nonlinear transformer inductance is established and more accurate equations for determining equivalent parameters are derived. On the basis of the dynamic model, the Weber-Ampere characteristic of the transformer core with instantaneous values of currents and flux-currents is constructed. Boundary conditions of ferroresonance stability and determination of boundary values of network capacitance are given on the example of calculation of equivalent parameters of energy-saving power voltage transformer TMG12-250/35

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

Текст научной работы на тему «FERRORESONANCE IN ELECTRICAL NETWORK 6-35 kV»

FERRORESONANCE IN ELECTRICAL NETWORK 6-35 kV

Begmatov Shavkat Ernstovich

Tashkent State Technical University, Uzbekistan https://doi.org/10.5281/zenodo.11068033

Abstract. Ferroresonance in 6-35kV electrical networks and the cause of power voltage transformer damage are considered. To study ferroresonance, a reliable dynamic model of nonlinear transformer inductance is established and more accurate equations for determining equivalent parameters are derived. On the basis of the dynamic model, the Weber-Ampere characteristic of the transformer core with instantaneous values of currents and flux-currents is constructed. Boundary conditions of ferroresonance stability and determination of boundary values of network capacitance are given on the example of calculation of equivalent parameters of energy-saving power voltage transformer TMG12-250/35.

Keywords: 6-35kV electrical network, ferroresonance, power voltage transformer, nonlinear inductance, dynamic model, equivalent parameters, Weber-Ampere characteristic, boundary conditions of ferroresonance stability.

INTRODUCTION

In a power supply system with 6-35kV distribution networks, under certain conditions ferroresonance (FR) occurs, as a result of which power voltage transformers (PVT) are damaged.

According to statistics, in various accidents in 6-35kV networks, PVTs account for about 80% of the damaged equipment. At the same time, about 10 per cent of installed PVTs are damaged annually in earth faults and FR. Practice confirms that FR between the network capacitance and the non-linear inductance (NI) of the transformer is often the cause of damage. As a rule, FR leads to overvoltages on the network busbars, and inadmissible currents flow through the PVT high voltage winding, which leads to their damage (Fig.1) [1-3].

Figure 1. Box of damaged transformers Taking into account that 6-35kV distribution networks are the longest in the power supply system, one of the special aspects of increasing the reliability of power supply is the study of modes of occurrence and determination of boundary conditions of stability of FR between the network capacitance and inductance of PVT.

RESEARCH METHODS AND THE RECEIVED RESULTS

The task of investigating FR is complicated by the fact that in high voltage 6-35kV electrical networks in conditions of limited application of experimental approaches due to the high cost of PVT, the creation of a reliable mathematical model of NI transformers and determination of boundary conditions of FR occurrence come to the forefront [4-5].

In works [6-9] mathematical models of transformers NI are proposed taking into account the influence of nonlinear parameters of PVT windings. However, in the proposed models, the analytical expressions are complex and do not accurately describe the dynamic mode of PVT operation under FR. Taking into account that FR is characterised by nonlinear jumping modes of saturation of the PVT core, it is urgent to create:

A dynamic model of the transformer NI;

Weber-Ampere Characteristic (WAC) of the NI, reflecting the dynamic hysteresis loop of the transformer core;

More accurate analytical equations for determining the parameters of the transformer NI.

As it is known, the process of transformer core remagnetisation can be represented by the dependence of magnetic induction (b) and magnetic field strength (h) in the following form [1011],

b = F

, dh h,—, dt

db d^b_ ' dt' dt2 :

(1)

Practically, expression (1) can be applied as a relationship between current (i) and flux-current (y) in the form of (2), which describes the dynamic NI model of the transformer (Fig.2) [12-15],

i

i = F

V, V

, dw dV ' dt ' dt2 '

i

(2)

u

Figure 2. Dynamic model of NI transformer

Where, Ls - dissipation inductance, Ce - electromagnetic capacitance, ge - active conductance, which are equivalent parameters of NI transformer. L(i)- inductance determined by the magnetic permeability of the ferromagnetic material of the transformer core.

From the condition of constancy of equivalent parameters and taking into account (2) on the basis of Kirchhoffs 1-law i=ic+ig+iL+is we receive

. d w dw , n V

i = Ce—2- + ge-?- + aw + bW + f-dt dt L„

(3)

Here, iL = a^ + byn - is the approximation of the NI WAC obtained from the magnetisation curve B=f(H) of the transformer core. If we assume that the voltage u = Umcosat and ^ = Wmsina>t, and taking into account the adopted approximation, we

obtain

U 1

is = T= a = i~ ;

ic = —a>2CeK¥m sin cot = —ICm sin cot; ig == g^cosct = Igm cos ct.

(4)

From (4) we have

gm

m

Ic

, = +1gm 2

2

(5)

m

iT = au + bun,

Taking into account equations (4) and (5), equation (3) will take the form

i =

a — -

I

cm

m

bun±

n^gm

m

-V^m—u

2

(6)

Based on equation (6), the hysteresis loop of the dynamic model of the NI transformer (Fig.3) can be plotted [10].

W

Figure 3. Hysteresis loop of the NI transformer dynamic model

Active equivalent conductivity ( ge) is determined from the dynamic coercive force

H of the transformer core. If, current Igm equals

cd

I = Ug = Hcd- = L Hc + 0,125ccd 2 B„V 2e —l)

gm e w c „ >

(7)

then from (7) we have

g = l He + 0,125<ccd2 BsV 2s-l) cow2 SB (8)

where, B - saturation induction, H - coercive force, d - thickness of magnetic material, s e

B

s - specific electrical conductivity of magnetic material, a = - core modulation factor

B

w - number of winding turns, l - average length of magnetic core.

We calculate the equivalent electromagnetic capacitance (Ce) and dissipation inductance (Ls) from the condition = Wr = wSB and i=0. Then, from equation (6) we obtain

= ayr + byrn -agj^im - W2 (9)

rn 2Wr

L - (10)

Ls

— (IcmVr + Vm - vj ) - bV?n

The equivalent nonlinear core inductance L(i) is determined from equation (6) assuming iy = *¥m = wSBm and i=0,

l (a \yr + b \yr )

As a result of analysing the dynamic model of the NI transformer, more accurate analytical equations (8),(9),(10) and (11) are obtained to determine the equivalent parameters ge, Ce, Ls and L(i) of the NI transformer. These equations prove that the equivalent parameters depend on both electrical and geometrical quantities as well as magnetic quantities of the transformer [14-15].

Considering that, in the FR mode, the saturation of the PVT core occurs and the input resistance of the network is capacitive, it is important to determine the boundary conditions for the stability of the FR [16].

Condition 1. The stability of FR is determined by the equivalent capacitance Ce of the network, which must be within the variation of the equivalent inductance PVT, i.e.

1/4TT2/2 < Ce < / 4tt2/% (12)

where,

Lj - is the PVT no-load inductance;

Lr- inductance of incomplete saturation of PVT core;

f - frequency of mains voltage.

If we assume that in the FR mode, the PVT core reaches incomplete saturation (± yr)

(Fig.3), then the no-load inductance Lo determine by the formula,

L0 = Unf/Io*(*i (13)

where,

Io - PVT idle current;

Unf - the nominal phase voltage of the PVT.

Under the same conditions (±y/r) (Fig.3), the inductance of incomplete saturation LT of the transformer core can be determined by the following equation,

Lr= l,3(nwz/4*dz Ka ^/a) (14)

iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.

where,

w - number of turns of the primary winding; d - average diameter of the winding; a - winding height;

- coefficient of winding shape;

Hq - relative magnetic permeability of air.

Condition 2. The FR remains stable within the limits of the variation of the flux-coupling y(i) in the ±^r and ±ym hysteresis loop of the dynamic model of the transformer NI (Fig.3),

i.e.,

± II * Lr (i) < y(i) < ± iL * L (i) (15)

It should be noted that the stability condition of FR according to (12) and (15) depends on the magnetisation curve B=f(H) or y=f(i) of the core magnetosheet and equivalent parameters of transformers.

To determine the boundary conditions of stable FR, the calculation of boundary values of capacitance is considered Ce network on the example of energy-saving three-phase two-winding PVT of TMG12-250/35 brand with reference data (Table 1).

Table 1

Sign CTH Snotm? kVA Catalogue data Calculation data

Unom. kV - windings Uk % APk kVt Po kVT Io % Rt Ohm xt Ohm

HV LV

TMG12 -250/35 250 35 6 4,50 3,25 0,425 2,30 11,70 40,50

Geometric data

w -number of primary winding turns dc. mm - average diameter of primary winding dn mm -primary winding outer diameter a mm - average winding height Ka -winding shape factor - relative magnetic permeability of air

21150 100 170 96 0,5615 12,56 * 10-7

1. Use formula (13) to find the no-load inductance of the transformer

Lo= 6000/0,23 *314 = 83,1 H

2. Use formula (14) to calculate the inductance of incomplete saturation of the transformer core

Lr = 1,3- ( 3,14- 211502/ 4-1002- 0,5615- 12,56- 10"7/ 96 )= 25,8 H

3. Taking into account the values Lo = 83,1 H u Lr = 25,8 H, according to equation (12) determine the boundary values of the capacity of the network Ce with one transformer TMG12-

250/35

1/4 * 3,142*502*83,1 <C3< 1/4 * 3,142* 502*25,8

or

12,2 nF < Ce < 157,2 nF (12.1)

4. Determine the boundary conditions for a group of seven PVTs of TMG12-250/35 brand with cascade connection, taking the winding parameters equal (Table 1):

85,4 nF <Ce< 1100,4 nF The boundary values of the network capacitance Ce (12.1) obtained as a result of calculation determine the condition of possible occurrence of stable FR on PVT of TMG12-250/35 brand. Beyond these values ferroresonance can be avoided, which is an important indicator for protection of transformers against possible overvoltages in the electric network.

The study of causes, effects, modes and boundary conditions of ferroresonance in a 6-35kV electrical network can be summarised as follows:

1. A dynamic model of NI transformer is proposed taking into account the equivalent parameters ge, Ce, Ls and L(i) (Fig.2).

2. Based on the dynamic NI model, a WAC reflecting the dynamic hysteresis loop of the transformer core is constructed (Fig.3).

3. More accurate analytical equations for calculation of equivalent parameters are obtained ge, Ce, Ls and L(i), which depend on both electrical and geometrical as well as magnetic parameters of the transformer.

4. Boundary conditions of FR stability and determination of boundary values of network capacity are given Ce on the example of calculation of equivalent parameters of energy-saving three-phase two-winding PVT of the brand TMG12-250/35.

CONCLUSION

Thus, FR is a special case in the power supply system and is observed in asymmetrical modes of electric networks, especially at incomplete phase switching of network sections.

In electric networks with voltage 6-35kV with isolated neutral, FR leads to the increase of flux-coupling on windings of each phase and deep saturation of PVT core. As a result, the increase in the maximum permissible value of magnetising current and, accordingly, voltage leads to overheating of windings and destruction of PVT (Fig.1).

The transformer core magnetization curve (Fig.3) takes into account the variation of instantaneous values of electrical and magnetic quantities, as well as equivalent parameters ge, Ce, Ls u L(i) NI in the dynamic mode of PVT operation.

Calculation of steady FR boundary conditions allows to determine the inductive parameters (!■„, Lr) of PVTs of different brands and the boundary values of capacitance (Ce) of high voltage electrical networks.

REFERENCES

1. Antonov N.A. Analysis of ferroresonant circuits of 110 - 500 kV electrical networks by the

methods of the athematical modeling. Dissertation 05.14.02. - Ivanovo, 1988. - 200c.

2. Vergara Valdes L.A. Development of a technique for detecting and compensating nonlinear dynamic processes in the medium voltage networks of the electrical complexes. Dissertation. Ph.D.: 05.09.03. - Moscow, 2016. - 161c.

3. Peng A. S. Ferroresonance simulation studies of transmission systems: PhD in Electrics and Electronic Engineering / A. S. Peng. - Manchester, UK: The University of Manchester, 2010. - 271 p.

4. Organization Standart 56947007-29.240.10.248. Norms of technological design of 35 -750

kV AC substations. - M.: PJSC "FSC UES", 2017. - 135 p.

5. Saenko Y.L., Popov A.S. Investigation of ferroresonance processes with regard to varying

the Weber -ampere characteristic of voltage transformers // Technical Electrodynamics.

2012. - № 6. - pp. 51-57.

6. Burgess R. Minimising the risk of cross - country faults in systems using arc suppression

coils / R. Burgess, A. Ahfock // Works of University of southern Queensland. - Australia. 2011. - N 7. - P. 703-711.

7. Analyzing ferroresonance phenomena in power transformers including zinc oxide arrester

and neutral resistance effect / H.Radmanesh, G.B.Gharehpetian, F.S.Hamid - Cairo: Hindawi Publishing Corporation, 2012. - 4 p.

8. Resistive ferroresonance limiter for potential transformers/H.Radmanesh, G.B.Gharehpetian, F.S.Hamid. - Iran.: Amirkabir University of Technology, 2012. - 6 p.

9. Bronzeado H.S. Review of ferroresonance phenomenon on power systems: Practical

examples and experience with adopted solutions / H. S. Bronzeado, Z. Emin, L. Kocis, B.Shim // Cigre International Symposium on Assessing and Improving Power System Security, Reliability and Performance in Light of Changing Energy

Sources, At Recife. - Brail. - 2011. - 10 p.

10. Bakhtiyar Abdullayev, Shavkat Begmatov. Models of nonlinear elements of electrical circuits and systems. Monograph // Publisher: LAP LAMBERT Academic Publishing. 2023. London, United Kingdom. ISBN: 978-620-6-78803-4.

11. Alimov A. A., Nosirova D. A., Akbarov F. A., Muminov Kh. A. To the problem of the calculation capacity of the nonlinear inductance. Journal of critical reviews. ISSN-23945125 Vol 7, Issue 15, 2020.doi:10.31838/jcr.07.15.232

12. Sh.E.Begmatov and others. Study of ferroresonance using generalized models of passive nonlinear elements. Rudenko International Conference "Methodological problems in reliability study of large energy systems" (RSES 2020), 14 December 2020, https://doi .org/10.1051/e3sconf/202021601115.

13. Begmatov Sh. Research of Ferroresonance in 6-35 kV Electrical Networks Taking Into Account the Dynamic Model of Non - Linear Inductivity of Power Transformer // Proceedings of International Conference on Applied Innovation in IT Volume 11, Issue

1, 2023, Pages 273-27711th International Conference on Applied Innovations in IT, ICAIIT 2023; Koethen; Germany; 9 March 2023.

14. Sh.E.Begmatov Calculation of active power losses taking into account the nonlinear inductance of the voltage transformer // TECHNICAL SCIENCE AND INNOVATION. № 3/2023. 137-144р. Tashkent State Technical University University.

15. Analysis of Ferroresonance in 6-35 kV Electric Networks Including Dynamic Model of Non-Linear inductivity of Power Transformer Shavkat Begmatov, Dilshod Khalmanov,

Saidakhon Dusmukhamedova, Elerjan Nabizhonov. Cite as: AIP Conference Proceedings 2552, 040011; https://doi.org/10.1063/5.0130666 Published Online: 05 January 2023.

16. Begmatov Sh.E. (Program for determining the boundary conditions of ferroresonance in transformers) Certificate No. DGU 24130. 03/24/2023. Republic of Uzbekistan.