Научная статья на тему 'AN OPTIMIZATION ALGORITHM TO DETERMINE APPARENT POWER OF ACTIVE FILTER'

AN OPTIMIZATION ALGORITHM TO DETERMINE APPARENT POWER OF ACTIVE FILTER Текст научной статьи по специальности «Электротехника, электронная техника, информационные технологии»

CC BY
28
17
i Надоели баннеры? Вы всегда можете отключить рекламу.
Ключевые слова
ACTIVE FILTER / ALGORITHM / HARMONIC / LOAD POWER FACTOR / POWER QUALITY INDEX

Аннотация научной статьи по электротехнике, электронной технике, информационным технологиям, автор научной работы — Kovernikova Lidia, Bui Ngoc Hung, Voitov Oleg, Semenova Lyudmila, Pham Duc Tien

The coal grading plants in Viet Nam extensively apply induction motors. Induction motors consume active and reactive power from the power supply systems. The reactive power flowing through the electrical network creates active power losses. The reactive power received from power utilities reduces the load power factor at the node where coal sorting plants are connected to the supply network. Frequency-controlled induction motors introduce distortions into the electrical network because they are electrical equipment with a nonlinear current-voltage characteristic. Non-sinusoidal current and voltage cause additional losses of active power in the electrical network and electrical equipment, thereby shortening its service life, reducing the reliability of operation, and causing economic damage. Active filters can solve these problems. The paper proposes an optimization algorithm for determining the apparent power of the active filter, which provides the load power factor and power quality indices corresponding to the regulatory documents. The algorithm is used to calculate the apparent power of the active filter for the coal grading plant owned by the Vietnamese company “Cua Ong-Vinacomin."

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

Текст научной работы на тему «AN OPTIMIZATION ALGORITHM TO DETERMINE APPARENT POWER OF ACTIVE FILTER»

An Optimization Algorithm to Determine Apparent Power of Active Filter

L.I. Kovernikova1, 2*, Bui Ngoc Hung2, 3, O.N. Vojtov1, L.V. Semenova1, Ha Thi Chuc3, Pham Duc Tien4

1 Melentiev Energy Systems Institute of Siberian Branch of Russian Academy of Sciences, Irkutsk, Russia

2 Irkutsk National Research Technical University, Irkutsk, Russia

3 Ha Noi University of Mining and Geology, Ha Noi, Viet Nam

4 Wong Bi - TKV - Vinasovin Coal Company, Ha Noi, Viet Nam

Abstract — The coal grading plants in Viet Nam extensively apply induction motors. Induction motors consume active and reactive power from the power supply systems. The reactive power flowing through the electrical network creates active power losses. The reactive power received from power utilities reduces the load power factor at the node where coal sorting plants are connected to the supply network. Frequency-controlled induction motors introduce distortions into the electrical network because they are electrical equipment with a nonlinear current-voltage characteristic. Non-sinusoidal current and voltage cause additional losses of active power in the electrical network and electrical equipment, thereby shortening its service life, reducing the reliability of operation, and causing economic damage. Active filters can solve these problems. The paper proposes an optimization algorithm for determining the apparent power of the active filter, which provides the load power factor and power quality indices corresponding to the regulatory documents. The algorithm is used to calculate the apparent power of the active filter for the coal grading plant owned by the Vietnamese company "Cua Ong-Vinacomin."

Index Terms—Active filter, algorithm, harmonic, load power factor, power quality index.

* Corresponding author. E-mail: kovernikova@isem.irk.ru

http://dx.doi.org/10.38028/esr.2021.01.0003 Received March 05, 2021. Revised March 07, 2021. Accepted March 13, 2021. Available online May 26, 2021.

This is an open access article under a Creative Commons Attribution-NonCommercial 4.0 International License.

© 2021 ESI SB RAS and authors. All rights reserved.

I. Introduction

Coal mining is one of the most important economic industries of Viet Nam. Mines and quarries have coal grading plants. Induction motors, primarily with frequency control, drive the manufacturing equipment of the plants. They are nonlinear loads for the power supply

system and distort power quality. The harmonic factors of voltage exceed the established standards [1]. Voltages and currents contain both harmonics and interharmonics [2]. The load power factors are lower than the value established by the normative documents [3].

In [4-7], the authors determine the active filter power to reduce the voltage and current harmonics in the electrical network. The power of the active filter is not only determined by the power of the harmonics. The use of the active filter is not confined only by the need to reduce harmonic values. Many consumers have additional economic losses because their electrical equipment receives reactive power from the supply network. In this context, the load power factor at the node connecting the power supply system of consumers to the supply network is lower than the standard value established for consumers. In [8-11], the authors use the active filter to compensate for reactive power and reduce harmonics. The authors of these papers do not consider active power losses due to reactive power transmission through the electrical network. Consumers have to pay for these losses and thus face additional economic damage. In [12-15], the authors determine the power of active filter to compensate for reactive power and reduce the values of harmonics, thereby providing the minimum losses of active power during the transmission of reactive power and the flow of harmonic currents in the electrical network of the power supply system.

The paper is concerned with an analysis of the power supply system of the coal grading plant, and results of the power quality tests. It formulates an optimization

Table 1. Measured SU, Kv, %.

Parameter Phase A Phase B Phase C

SUmax 4.1 4.5 4.6

SUmn_-1.3_-17_-1.4

\SUnorm\_< 5.0_

Kumax_16.8_15.3_17.1

K Unarm < 6.5

0 EPS

22 kV — — 6643 Coal grading plant

(A f\ 45038 k) 1000 kVA "J 22/0.4 kV - 4143 \ 45039 \ 45041

Sho ! V p No.1 Shop No.2 \ Cc ware] V '„1 Electricity and water supply shop -■ louse 450 k VAr

Fig. 1. Power supply .system of the coal grading plant.

problem, describes an algorithm to determine the apparent power of the active filter, and presents specially designed software and results of the active filter apparent power calculation for the coal grading plant of the company "Cua Ong-Vinacomin."

II. Characteristic of the power supply system and

LOADS OF THE COAL GRADING PLANT

Fig.1 presents a scheme of the power supply system of the coal grading plant.

Electrical power from the 22 kV substation buses of the power supply utility (node 6643) is supplied to the 0.4 kV network of the power supply system of the coal grading plant (node 4143) by the 1000 kVA step-down transformer that belongs to the plant. The distance between nodes 4143 and 45038 is 60 meters. The total length of the 0.4 kV electrical network exceeds 12 km. The plant has two coal grading shops (shop No.1, shop No. 2), a shop of electricity and water supply, and a coal warehouse. Coal is mined in the quarry and transported to the warehouse of the coal grading plant. In the warehouse, the excavator unloads coal on the conveyor. The conveyor delivers coal to the shops for grading it by size. Fifty-eight induction motors with a capacity of 4 to 185 kW put the technological equipment of the shops into operation.

The following indices and norms for their values were established in [1] to assess voltage and current values in the 0.4 kV network:

• the voltage deviation |5U < 5.0%;

• the total harmonic distortion KT < 6.5%;

• the h-th harmonic factor of voltage KU(h) < 3%;

• the h-th harmonic factor of current KI(h) < 12%.

In [2], the load power factor (cos 9) at the connection node of the plant to the supply network should meet the condition cos 9 >0.85. If this condition is not fulfilled, the company, owner of the plant, pays penalties to the power

Table 2. Measured KU(h), Km, %.

Parameter Harmonic

3 5 7 11 13 17 23

Ku(h)maxA 2.5 12.7 12.8 4.6 2.1 3.3 3.1

Ku(h)maxB 3.9 12.3 11.8 4.6 3.1 2.7 2.8

Ku(h)maxC 2.0 12.3 12.8 3.6 2.8 3.4 3.4

Ku(h)norm < 3.0

KlKimamt 7.1 6.8 6.7 3.9 1.9 2.3 2.7

Kl{ti)maxB 3.9 4.2 1.7 0.8 1.1 0.5 0.4

Kl(h)maxC 3.6 4.9 3.3 1.2 1.7 1.5 1.2

Kl(h)iorm < 12.0

Table 3. Measured Ku(M), %, I(M), A.

Parameter Interharmonic

1.5 3.5 5.5 7.5 17.5 19.5 21.5

3.9 1.0 1.7 1.8 1.2 1.5 2.3

Ku(m)maxB 3.3 0.8 1.9 1.9 1.0 1.3 2.3

Ku(m)maxC 3.8 0.9 0.9 1.2 1.7 1.7 1.7

I(m)maxA 16.6 6.0 5.1 4.3 7.5 8.5 9.6

I(m)maxB 17.2 4.8 5.0 2.7 1.9 2.7 3.2

I(m)maxC 18.0 7.3 6.4 5.3 9.2 9.7 7.5

Table 4. Measured cos 9, p.u.

Parameter Phase A Phase B Phase С

cos 0.98 0.92 0.99

cos 9min 0.89 0.72 0.89

COS q„orm >0.85

supply utility. The value of cos 9 can be low because of large reactive power consumption by the electrical motors of the plant, active power losses when transmitted over the electrical network, and losses caused by harmonics and interharmonics. Power quality indices and the value of cos 9 at node 4143 were tested.

III. Results of the electrical energy tests

The tests included 24-hour measurements of the voltage and current quality indices and cos 9 by the device PQ-Box150 [16] with a time interval of measurements equal to 1 second.

Table 1 presents the measured values of 5U, which meet the requirements [1]. The Table also shows the measured values of KU and their normative values from [1]. The measured values of KU exceed the norm more than twice. They are shown in bold type.

Table 2 presents the measured and normative values of KTm and KI(h) for the harmonics that exceed the norms

r- 4

Start

,_ 1

Input initial information on the scheme

Assign the number of regulating transformer tap k

Assign the reactive power of the active filter Qaf

Calculate the load flow

V

Calculate Qaf

r 5

no

no

Calculate the total active power losses in the network AP(i)

no 11

r 12

^ yes

Calculate the apparent harmonic power

13 *

Calculate the apparent interharmonic power

*

14 Calculate the apparent power of the active filter

15 *

Obtain calculation results

End

Fig. 2. Block-diagram of the algorithm to determine the power of the active filter.

2

3

8

Program to calculation the active filter power (AF)

File of SDO calculation results

Input voltage at the connection node: kV

iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.

Analysis ofthe entered information

Nodes Lines

Calculation of the mode of the electrical network

Lines Nodes

Calculated A P Calculated Umin - Umax

Fig. 3. Sheet 1 of the program.

most frequently [1]. The measured values of KI{h) are not connecting the plant to the supply network; KU{h) f is the higher than the normative value.

The measured values of KU(m) for some interharmonics and the values of currents /(m)max of these interharmonics (m - the number of the interharmonic) are given in Table 3. The normative values for them are not determined.

The measured values of cos 9 and its normative value determined in [3] are shown in Table 4. At phase В, the value of cos 9 is lower than the norm.

The problems caused by harmonics, interharmonics, and cos 9 can be resolved using a shunt active filter connected to the network in parallel to the nonlinear load [7-15, 17-20].

IV. Optimization problem to determine the power

of the active filter The power of the active filter is determined by the reactive power to be generated to compensate for the reactive power of load and apparent power required to get rid of harmonics and interharmonics of the current at the point of the filter connection to the network. This can be achieved by solving an optimization problem with the objective function assumed to be the minimum active power losses in the power system network after installation of the active filter, i.e.,

H M

ZAPW + ZAP = min , d)

h=1 m=1 2

where H is the highest number of the harmonic, (M - 1/2) is the highest number of interharmonic. In this case, the following constraints are to be met

0.95 < cos 9 < 1.0, (2)

(3)

(4)

(5)

(6)

where i is the network node number; Ui is the voltage of the fundamental frequency; Umin, Umax are the normative minimum and maximum voltages of the fundamental frequency; cos 9 is the load power factor at the node

U ■ < U- < U

min — i — max> KU(h)min < KU(h) f < KU(h)max, KUmin < KU f < KUmax, KI(h)min < KI(hf < KI(h)max,

h-th harmonic factor of voltage after installation of the active filter; Ku{h)mm, Ku{h)mœc are the normative maximum and minimum of the h-th harmonic factor of voltages; Kuf is the total harmonic distortion after installation of the active filter; KUmm, KUmax are the normative maximum and minimum of the total harmonic distortion; KI(h)f is the h-th harmonic factor of current after installation of the

actrve filter; Kmm,m> KI(h)max are the normative maximUm

and minimum of the h-th harmonic factor of current. Constraint (2) was established by the company "Cua Ong-Vinacomin".

The optimization problem consists of three subproblems:

1. calculation of the apparent power of the active filter to provide the normative cos 9;

2. calculation of the apparent power of the active filter to eliminate current harmonics;

Table 5. QAF and AP(1)E calculated by the algorithm.

U4143, kV Qaf , kVAr AP(i)i, kW

0.38 350 297

0.39 480 290

0.40 330 192

0.41 450 134

0.42 580 110

Table 6. Umin, Umax, and cos 94143 calculated by the algorithm.

U4143, kV COS ^4143, p.U. Umin, kV Umaxi kV

0.38 0.98 0.38 0.39

0.39 0.97 0.38 0.39

0.40 1.00 0.38 0.39

0.41 0.99 0.38 0.41

0.42 1.00 0.38 0.41

Table 7. Active, reactive, and apparent powers of harmonics.

Parameter Phase A Phase B Phase C

Ph, kW 8.9 6.9 7.2

Qh, kVAr 11.0 7.3 14.4

Sh, kVA 14.1 10.1 16.1

Power calculation So

Input voltage at the connection node:

kV

Power Sg

Calculation of power compensation

Calculated

Omin U O max

Calculation of Umin, Umax for compensation power

Calculation of active power losses A P

Active power A P

AF placementnode

Node number

Calculationresults

So, node number of minimun A P

Calculated

Umin, Umax

Fig. 4. Sheet 2 of the program.

3. calculation of the apparent power of the active harmonic

filter to eliminate current interharmonics.

The first subproblem is formulated as follows: minimize the total active power losses in the network at the fundamental frequency, i.e.

AP(1) = min. (7)

In this case, constraints (2) and (3) should be fulfilled. If a node for active filter installation is not assigned, all nodes of the network must be considered as candidates for installation. The algorithm must consider transformer capabilities of voltage control on the lower side with the connected load. The suggested algorithm was developed based on the software "SDO" to calculate the fundamental frequency load flow [21-22]. The block diagram of the algorithm is presented in Fig. 2.

Block 1. Input initial information on the electrical network scheme.

Block 2. Assign the number of transformer tap k, k = 1, K, K is the quantity of taps.

Block 3. Assign the reactive power value of the active filter at the first step QAF = 0.

Block 4. Calculate the load flow.

Block 5. Calculate cos 9 at the connection node of the power supply system of the plant to the supply network based on the results of calculation using the expression cos = P ij /^1 Pj + Qj, where "c" is an abbreviation of "calculated," Pj and Qy are the active and reactive powers, i,j are the network node numbers.

Block 6. Test fulfillment of constraint (2). If it is fulfilled, go to Block 7, otherwise, go to Block 8

Block 7. Test fulfillment of constraint (3) at all network nodes. If it is fulfilled, go to Block 9, otherwise, go to Block 8.

Block 8. Calculate the reactive power of the active filter. The reactive power is calculated as

qaf = pj (tg 9c - tg 9d),

where "d" is an abbreviation of "desired." The value of tg 9C is determined based on cos 9c. The value of tg 9d is calculated using constraint (2). Since the feasible value of cos 9 is within the interval

cos 9m,n < cos 9 < cos 9 the value of the reactive power of the active filter is also within the interval

Qmin < QaF < Qmax'

The required phase angle 9d should be calculated using cos 9min and cos 9max. The highest and lowest values of QAF are calculated by the expressions

Qmin = Pj (tg 9 c - tg 9,^

Qmax = P (tg 9c - tg 9 max).

Block 9. Calculate the total active power losses in the network based on the load flow calculation.

Block 10. Compare the active power losses of the preceding calculation step with the losses of the current step to determine minimum losses, namely, if AP0) < APmm, then AF„iin = AP(j).

Block 11. Change the number of the transformer tap k = k + 1. If k > K, then go to Block 12, if the condition is not fulfilled, go to Block 2.

Block 12. Minimize the active power losses caused by

H

harmonics in the network, i.e., ^ DP( h) = min.

h=2

In this case, constraints (4)-(6) should be met by eliminating the harmonics of current with the help of the active filter at the node of filter connection. The apparent harmonic power is calculated as Sh6 + Qh [23], where

H

Ph = YUhJh cos,

h=2

H

Qh = YUhJh Sin

h=2

iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.

were calculated by the measured voltages Uh, currents Ih and phase angle 9h.

Fig. 5. Sheet 5 of the program.

Block 13. Minimize the active power losses caused by the interharmonics in the network, i.e.,

M

i, =min.

For this purpose, the interharmonics of current should be eliminated by the active filter at the node of filter connection. The apparent power of interharmonics

M

is calculated as SmZ = ^ Um+1l2Im+1/2 by the measured

m=1

voltages Um and currents Im.

Block 14. Calculate the apparent power of the active filter as a sum of three powers:

SAF = SQAF + SKZ + Sm£.

Block 15. Obtain calculation results.

V. The computer program to calculate the active filter power

The computer program [24] was developed based on the algorithm built to determine the active filter power presented in Fig. 2. It is written in MS Excel and the programming environment Visual Basic for Windows applications. The program is designed to determine the apparent active filter power to compensate for the reactive load power for improving the power factor, and eliminating harmonics and interharmonics. The program makes it possible to determine a network node for placing an active filter.

The computer program component of the mentioned software "The stationary feasible optimal condition" (the software "SDO") is applied to calculate the value of power to be generated by the active filter for compensation for the reactive load power and to determine the network node for installation of the active filter [20-21]. This software is intended for the calculation of the steady-state conditions in electrical networks. It implements algorithms for calculation of feasible and optimal conditions in terms of the active and reactive power losses in the electrical

networks with different voltage levels, including the steady-state unbalanced conditions of low-voltage distribution networks.

The program for calculation of active load power filter consists of five MS Excel sheets: sheet 1 is "Primary", sheet 2 is "Power QAF", sheet 3 is "Harmonics power Sh", sheet 4 is "Interharmonics power Sm", sheet 5 is "Power SAF". Figure 3 presents the first sheet as an example. The fundamental frequency load flow and the comparative evaluation of cos 9 and Uk values, which were measured and calculated using the software "SDO" at the node connecting the power supply system of the plant to the supply network, were calculated using the commands of the first sheet. Comparison of the calculated parameters with the results of measurements and their close values confirms that modeling of the electrical network for calculation of the reactive power value was correct.

The reactive power value consumed by the load generated by the active filter is calculated in sheet 2 (Fig. 4). The electrical network node for the installation of the active filter is identified through calculation. If the node is determined correctly, the active power losses in the network elements will be minimal.

Table 8. Apparent powers of interharmonics.

Sm,VA Interharmonic

1.5 3.5 5.5 17.5 19.5 11.5

Phase A 16.6 6.0 5.1 7.5 8.5 5.1

Phase B 17.2 4.8 5.0 1.9 2.7 3.7

Phase C 18.0 7.3 6.4 9.2 9.7 5.0

SmZA,B,C 51.8 18.1 16.5 18.6 20.9 13.8

Sm,VA Interharmonic

13.5 21.5 23.5 25.5 27.5 29.5

Phase A 5.1 9.6 13.1 12.5 7.0 7.5

Phase B 2.2 3.2 3.0 2.7 1.9 1.4

Phase C 5.2 7.5 5.7 6.5 3.8 3.6

SmzA,B,c 12.5 20.3 21.8 21.7 12.7 12.5

The apparent power values of harmonics and interharmonics to be eliminated by the active filter are calculated in sheets 3 and 4. The powers are calculated by the results of measurements of harmonic load flow parameters and power quality indices at the electrical network node chosen for the active filter installation.

The apparent power of the active filter is calculated in sheet 5 of the program. Sheet 5 with the Table of the calculation results is presented in Fig. 5. The Table indicates the number of the network node for installation of the active filter, the value of the minimum active power losses, the reactive power of the fundamental frequency, the harmonic power, the interharmonic power, and the apparent power of the active filter.

vI. Determination of the apparent power of the active filter harmonics for the coal grading plant of the company "cua ong-vinacomin"

The management company of the coal grading plant has chosen node 45038 for the installation of an active filter in the power supply system (Fig. 1). The transformer supplying electrical power to the power supply system of the plant has five taps. They make it possible to have the voltages of 0.38 kV, 0.39 kV, 0.4 kV, 0.41 kV, and 0.42 kV at node 4143. The calculation results show that if the voltage at node 4143 changes from 0.38 kV to 0.42 kV, at 57 network nodes of 0.4 kV the voltages range from 0.36 kV to 0.39 kV. Hence, the requirements of [3] are not fulfilled. In this case, the load power factor at node 4143 takes the values from 0.88 to 0.99, which meets partially the company requirements. Thus, the generation of reactive power can increase the voltage at the system nodes and the load power factor at node 4143.

The computer program for calculating the active filter power following the proposed algorithm was applied to calculate the reactive power value of the active filter. The intermediate calculation results are presented in Tables 5 and 6.

The lowest active power losses in the network equal to 110 kW are observed with the tap of the 0.42 kV transformer and the reactive power of the active filter of 580 kVAr. All the voltage conditions at the network nodes and node 4143 are met.

Harmonic powers were calculated based on measured parameters and are shown in Table 7. The active filter must have no less than 16 kVA at each phase to eliminate harmonic currents. The total apparent power of harmonics in three phases is 40.3 kVA.

Table 8 presents the values of phase apparent power of some interharmonics and the total apparent powers of three phases, which were calculated by measured parameters. The total apparent power of interharmonics of three phases is 0.7 kVA, which is less than 1% of the harmonic power.

Figure 5 demonstrates the calculation results presented in the fifth sheet of the computer program. The Figure

shows that at node 45038 of the active filter connection, the active power losses in the electrical network of the coal grading plant will be minimal and equal to 110 kW with the transformer tap of 0.42 kV and the apparent power of the active filter of 621.1 kVA.

VII. Conclusion The measurements have shown that the load current contains harmonics and interharmonics, the indices KU{n) and Kv exceed the normative values, and cos 9 is lower than the norm.

Reduction in total harmonic distortion and increase in load power factor can be achieved with an active filter installed. The power of the active filter was determined using the developed optimization algorithm and measurements of load flow parameters.

The active filter power was determined for the coal grading plant of the company "Cua Ong-Vinacomin."

Acknowledgment

The research was carried out under State Assignment Project (No. FWEU-2021-0001) of the Fundamental Research Program of Russian Federation 2021-2030.

References

[1] Circular No.39/2015/TT-BCT of the Ministry of Industry and Trade of Viet Nam for the distribution of Electrical Energy

[2] Electromagnetic compatibility of technical equipment. A general guide on harmonics and interharmonics measuring instruments and measurement for power supply systems and equipment connected thereto, GOST 30804.4.7-2013 (IEC 61000-4-7:2009), ISC Standard, 2013.

[3] National Technical Regulation on Electric Power, Viet Nam, 2015.

[4] B. Singh, K. Al-Haddad, A. Chandra, "A review of active filters for power quality improvement," IEEE Transactions on Industrial Electronics, vol. 46, no. 5, pp. 960-971, 1999.

[5] Gong Maozhong, Liu Hankui, Gu Jianjun, Xu Dianguo, "Active power filter based on novel current reference calculation," in Proc. IEEE ICIT'02, Thailand, 2003, DOI: 10.1109/ICIT.2002.1189916.

[6] C. H. da Silva, V. F. da Silva, L. E. B. da Silva, "Evaluation of Power-Ratings for Active Series Filters under Unbalanced Conditions for a Three Phase -Four Wire System," in Proc. IEEE 36th PESC, Brazil, 2006, DOI: 10.1109/PESC.2005.1581638.

[7] Shekh Saddam Husen, Patel Pinkal J., "A literature review and industrial survey on active power filter,"

International journal of engineering development and research, vol. 2, no. 1, pp. 118-125, 2014.

[8] M.El-Habrouk, M.K. Darwish, P. Mehta, "Active power filter: A review," IEEE Proceedings in Electric Power Applications, vol. 147, no. 5, pp. 403-413, 2000.

[9] Salvador Orts; Francisco J. Gimeno-Sales; Antonio Abellan; Salvador Segui-Chilet; Miguel Alcaniz, Rafael Masot, "Achieving maximum efficiency in three-phase systems with a shunt active power compensator based on IEEE Std. 1459, " IEEE Transactions on Power Delivery vol. 23, no. 2, pp. 812-822, 2008, DOI: 10.1109/TPWRD.2007.915910.

[10] Abbas Mariani, Luigi Piegari, Saeed Saeedallah Mortazavi, Mohammad-Sadegh Ghazizadeh, "Active Power Filter Commitment for Harmonic Compensation in Microgrids," in Proc. IECON 2019 - 45th Annual Conference of the IEEE IES, Portugal, 2019, DOI: 10.1109/IECON.2019.8927668.

[11] A. Kouzou, B. S. Khaldi, S. Saadi, M. O. Mahmoudi, M.S. Boucherit, "Apparent power ratio of the Shunt Active Power Filter," in Proc. 13th International EPE-PEMC, Poland, DOI: 10.1109/ EPEPEMC.2008.4635557.

[12] Gary W Chang, "A New Method for Determining Reference Compensating Currents of Three-Phase Shunt Active Power Filters," IEEE Power Engineering Review, vol. 22, issue 4, pp. 68-70, April 2002, DOI: 10.1109/MPER.2002.4312116.

[13] Faegheh Irannezhad, Seyed Hossein Hosseinian, Mehrdad Abedi, Behrooz Vahidis, "Using the Instantaneous Power Theory in order to control the current in the parallel active filter to compensate reactive power and reduction of harmonics," in Proc. PEDES 2012, India, DOI: 10.1109/ PEDES.2012.6484390.

[14] Jun Yang, Yue Wang, Zhaoan Wang, "A DSP controlled hybrid power filter used to compensate the harmonics and reactive power caused by electrical traction loads," IEEE Cat. No.03CH37491, Canada, 2004, DOI: 10.1109/PES.2003.1267397.

[15] Izzeldin Idris Abdalla, K. S. Rama Rao, N. Perumal, "Three-phase four-leg shunt active power filter to compensate harmonics and reactive power," in Proc. ISCI, Malaysia, 2011, DOI: 10.1109/ ISCI.2011.5958965.

[16] Operating Manual Network Analyzer PQ-Box 150 Power-Quality Evaluation Software, A. Eberle GmbH, and Co. KG, 2017, [Online]. Available: https://www.a-eberle.de/sites/default/files/media/ BA_PQBox150_EN_ 201803.pdf (Accessed on Jan. 6, 2021).

[17] M. Maciazek, D Grabowski, and M. Pasko, "Active power filters - optimization of sizing and placement,"

Bulletin of the polish academy of sciences "Technical sciences," vol. 61, no. 4, pp. 847-853, 2013.

[18] Vahid Chakeri, M. T. Hagh, "Optimal Allocation of the Distributed Active Filters Based on Total Loss Reduction," Int. Journal of Smart Electrical Engineering, vol. 6, no. 4, pp. 171-175, 2017.

[19] Sarita Samal, Prakash Kumar Hota, Prasanta Kumar Bank, "Harmonics Mitigation by using Shunt Active Power Filter under Different Load Condition," in Proc. SCOPES, India, 2016, DOI: 10.1109/SCOPES.2016.

7955598.

[20] G. M. Mustafa, S. I. Gusev S.I. "Active filter-compensating devices of shunt and series type in electrical networks," Energetik, 2019, no. 8, pp. 3-10.

[21] O. N. Voitov, E. V. Popova, L. V Semenova, "Algorithms for load flow calculation in electric networks

in terms of the temperature of overhead line conductors and their implementation," Elektrichestvo, 2013, no. 3, pp.19-26.

[22] Certificate of conformity no. ROSS RU.SP20. N00008 "Software SDO-7 for analysis, optimization of steady states and evaluation of electric power losses in electric networks'' - Certificate scheme GOST R Gosstandart Rossii. Expiration date: from 31.01.2009 to 31.01.2012.

[23] A. E. Emanuel, "Three-Phase Nonsinusoidal and Unbalanced Conditions" in Power definitions and the physical mechanism of power flow, Worcester Polytechnic Institute, USA, IEEE PRESS, John Wiley and Sons, Ltd., Publication, 2010, pp. 185-203.

[24] Certificate of state registration of a computer program No. 2021613837 "Program for calculating the active filter power," Federal Service for Intellectual Property. Expiration date: from 15.01.2021 to 15.01.2035.

Lidia Kovernikova is a Senior Researcher of Melentiev Energy Systems Institute of the Russian Academy of Sciences, Irkutsk, Russia. She graduated from Novosibirsk Electrotechnical Institute in 1976. L.I. Kovernikova received her Ph.D. degree in engineering from the Siberian Energy Institute in 1995. Her research interests include modeling non-sinusoidal conditions of electrical power systems, analyzing the power quality in electrical networks, and developing technical means to improve the power quality.

Bui Ngoc Hung is a graduate student of Irkutsk National Research Technical University, Irkutsk, Russia. He graduated from Ha Noi University of Mining and Geology in 2006. Bui Ngoc Hung completed his Ph.D. in electrical engineering at Ha Noi University of Mines and Geology. His research interests include power quality in electrical networks and developing technical means to improve the power quality.

Oleg Voitov is a Senior Researcher of Melentiev Energy Systems Institute of the Russian Academy of Sciences, Irkutsk, Russia. He graduated from Moscow Power Engineering Institute in 1971. O.N. Voitov received his Ph.D. degree in engineering from the Siberian Energy Institute in 1993. His research interests include modeling the steady-state conditions of electric power systems in a single-line representation and phase coordinates, the development of algorithms for analyzing and optimizing instantaneous and short-term operating conditions in the context of discrete parameter changes.

Lyudmila Semenova is the Lead Engineer of Melentiev Energy Systems Institute of the Russian Academy of Sciences, Irkutsk, Russia. L. V. Semenova graduated from Irkutsk Polytechnic Institute in 1974. Her research interests include the development and implementation of methods and models for studying the functioning of power systems.

Pham Duc Tien is a power engineer at the Wong Bi - TKV - Vinasovin Coal Company in Viet Nam. He teaches at the College of Construction of the Ministry of Construction. He graduated from Ha Noi University of Mining and Geology in 2006. Pham Duc Tien completed his master's degree in electrical engineering at Ha Noi University of Mining and Geology. His research interests include power quality, development of technical methods to improve it, safety and operation of high voltage power supply.

Ha Thi Chuc is a lecturer at the University of Mining and Geology, Ha Noi, Viet Nam. She graduated from Ha Noi University of Transport and Communication in 2008. Ha Thi Chuc completed her Ph.D. in Electrical and Electronic Engineering at the Ha Noi University of Transport and Communication. Her research interests include power quality, developing technical means to improve the power.