Научная статья на тему 'PRACTICAL WAY FOR DETERMINING THE FIRE RESISTANCE OF SQUARE REINFORCED CONCRETE SECTIONS WITH A SYMMETRICAL REINFORCEMENT, SUBJECTED TO BIAXIAL BENDING AND ALL-SIDED FIRE EXPOSURE'

PRACTICAL WAY FOR DETERMINING THE FIRE RESISTANCE OF SQUARE REINFORCED CONCRETE SECTIONS WITH A SYMMETRICAL REINFORCEMENT, SUBJECTED TO BIAXIAL BENDING AND ALL-SIDED FIRE EXPOSURE Текст научной статьи по специальности «Строительство и архитектура»

CC BY
36
9
i Надоели баннеры? Вы всегда можете отключить рекламу.
Журнал
World science
Ключевые слова
FIRE RESISTANCE OF REINFORCED CONCRETE COLUMNS

Аннотация научной статьи по строительству и архитектуре, автор научной работы — Neshev Hristian

Beams and plates in reinforced concrete structures, subjected to internal, edge and corner columns to biaxial bending. Based on the simplified calculation method, “Isotherm 500°C,” in BDS EN 1992-1-2, are composed normalized interaction curves (nomograms) for determining the fire resistance of reinforced concrete square columns, subject of all-sided fire exposure. The nomograms are drawn up for columns, reinforced with four longitudinal bars at the corners of the section. Conclusions and recommendations are made for the practical application of the nomograms.

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

Текст научной работы на тему «PRACTICAL WAY FOR DETERMINING THE FIRE RESISTANCE OF SQUARE REINFORCED CONCRETE SECTIONS WITH A SYMMETRICAL REINFORCEMENT, SUBJECTED TO BIAXIAL BENDING AND ALL-SIDED FIRE EXPOSURE»

exact temperature of the concrete at each point of section [3], [4]. However, this method is more complicated for civil engineers to implement in practice;

d) the reinforced concrete sections design, computed by the simplified calculation method, "Isotherm 500°C", does not take into account the thermal expansion of material (concrete and reinforcing steel).

REFERENCES

1. БДС EN 1992-1-2:2005 и БДС EN 1992-1-2:2005/ NA - Еврокод 2: Проектиране на бетонни и стоманобетонни конструкции. Част 1-2: Общи правила. Проектиране на конструкции срещу въздействие от пожар.

2. Захариева-Георгиева Б. Проверка за огнеустойчивост на стоманобетонни колони чрез опростения изчислителен метод „Изотерма 500°С" на БДС EN 1992-1-2:2005, „сп. Строителство", бр. 6, 2012 г.

3. Нешев Хр., Михов Я. Носеща способност на стоманобетонни сечения със симетрична армировка, подложени на равнинен или кос нецентричен натиск при четиристранно пожарно въздействие, Първа научно- приложна конференция с международно участие. Стоманобетонни конструкции теория и практика- София, 2015г.;

4. Нешев Хр., Михов Я. Носеща способност на стоманобетонни колони със симетрична армировка, запънати в долния край и с пружинно ограничаване на температурното разширение в горния край, подложени на осова натискова сила при четиристранно пожарно въздействие, Първа научно- приложна конференция с международно участие. Стоманобетонни конструкции теория и практика- София, 2015г.;

5. Buyukozturk O. Mechanics and Design of Concrete Structures (3-0-9), Biaxial Bending,

6. http://ocw.mit.edu/courses/civil-and-environmental-engineering/1-054-mechanics-and-design-of-concrete-structures-spring-2004/lecture-notes/Outline_08.pdf

PRACTICAL WAY FOR DETERMINING THE FIRE RESISTANCE OF SQUARE REINFORCED CONCRETE SECTIONS WITH A SYMMETRICAL REINFORCEMENT, SUBJECTED TO BIAXIAL BENDING AND ALL-SIDED FIRE

EXPOSURE

Neshev Hristian

PhD Student, University of Architecture, Civil engineering and Geodesy, Sofia, Bulgaria, Department of Reinforced Concrete Structures

Abstract. Beams and plates in reinforced concrete structures, subjected to internal, edge and corner columns to biaxial bending. Based on the simplified calculation method, "Isotherm 500°C," in BDS EN 1992-1-2, are composed normalized interaction curves (nomograms) for determining the fire resistance of reinforced concrete square columns, subject of all-sided fire exposure. The nomograms are drawn up for columns, reinforced with four longitudinal bars at the corners of the section. Conclusions and recommendations are made for the practical application of the nomograms.

Keywords: fire resistance of reinforced concrete columns

1. Introduction. Reinforced concrete columns are subjected to biaxial bending (compressive force applied to eccentricity on two principal axes of the section) at:

- transmission of unbalanced moments from beams and slabs along the main axis of the section;

- eccentrically loaded footing from bearing elements;

- asymmetrical change to the section;

- taking into account the imperfections (accidental eccentricity) for each direction of the cross-section;

- taking into account the effects of the second order for each direction of the section.

This paper examines square columns, subjected to biaxial bending and all-sided fire exposure, using the simplified calculation method, "Isotherm 500°C" [1]. This method is based on the hypothesis that the concrete at temperatures higher than 500°C is damaged and this zone from cross-section is neglected in the calculation of the load-bearing capacity. Concrete at temperatures below 500°C is assumed to retain its full strength, equal to the strength at 20°C. Calculations are conducted based on a reduced section with dimensions h^ = h — 2.az, where az is the thickness of the damaged zone of

the fire exposed sides. The damaged zone can be determined based on the temperature profiles presented in Annex A [1], based on other specialized literature, by solving the differential equation of the Fourier heat conduction equation in solids, or by using specialized software, which calculates the temperature distribution in concrete elements.

2. Calculation of square concrete sections with symmetrical reinforcement, subjected to biaxial bending and all-sided fire exposure. Physical processes and chemical reactions are changing the physical and mechanical properties in concrete and are reinforcing the steel exposed to elevated temperatures. The characteristic value of yield strength fyy g for steel reinforcement decreases and the

coefficient ks (0i) for the reduced strength is reported in figure 4.2 in [1]. The design yield strength of the steel is determined by the formula fsd e= fy elys ^ = ks(#,■).fyk: l Ys ft? where fyk is the characteristic value of the yield strength at a temperature of 20 °C and ys fi = yc fi = 1 is the partial safety factor for the relevant material property (concrete and reinforcing steel) for fire exposure. The design compressive strength of concrete at elevated temperature is fcd fi = OCcc .fck / yC f . The design cylindrical compressive strength of concrete at elevated temperature is fd = acc .fck / yc fi .

The coefficient OCcc = 0,85 in the design of normal sections, bearing capacity of vertical or inclined elements, are implemented in a monolithic method [2]. Figure 1 shows the stages of heating a column, depending on the thickness of the damaged zone az and the distance, a . Three cases of the Isotherm

500°C position are defined:

a) a < a - longitudinal reinforcement is inside the undamaged area of the section and the

temperature is below 500°C;

b) az = a - bearing reinforcement is located on the Isotherm 500°C and the thickness of the

damaged zone az is equal to the distance, a ;

c) az > a - longitudinal reinforcement is outside the reduced cross-section and the

temperature is above 500°C.

Figure 2 presents the decrease in bearing capacity of the section with development of the fire exposure. This is due to the increasing thickness of the damaged zone, , and the reduction of the yield strength of reinforcement steel.

Changing angle by degrees of 1° (fig.2, fig.3) and using equations for statics to axes passing through the center of reduced (no reduced) square cross-section, normalized interaction curves (nomograms) for different relations are composed. The equations of statics are:

__n

^M = 0 -> M fiM = Kfi-Vfcdf • dc,fi + Z (*),< • ds,i,fi

i=1 (1)

__n

y H = 0 ^ Nf. Ed = A r.nf. f +y A . r.a,a,., (2)

/ ' fi,Ed c,fi IJ cd fi / ' s,i, fi s[Of,i

i=1

where: <j . - are stresses in any longitudinal rebar with area As i f in the fire exposure; Aci fi - is the area of the compression zone in the cross-section;

dc f - is the distance from the center of gravity of the compression zone to the axis, passing

through the center of gravity of the section;

- is the distance from the center of gravity of each longitudinal rebar to the axis, passing

s,i, fi

through the center of gravity of the section;

Fig. 1. Basic parameters and symbols in square column, subjected to biaxial bending and all-sided fire exposure, according to [1] at: a) a < a ; b) a = a ; c) a > a

Fig. 2. Interaction curves of a square column, subjected to biaxial bending and all-sided fire exposure

The assumptions and validity of the proposed normalized interaction curves (nomograms) are:

- Hypothesis of Bernoulli - cross-sections, planar and perpendicular to the longitudinal axis of the element, remain planar and perpendicular after a deformation;

- shear deformations are very small and therefore are ignored;

- when, the longitudinal reinforcement is outside of the reduced cross-section and the temperature is above 500°C. It is assumed that the stability of the longitudinal reinforcement is provided by the steel stirrups and concrete, heated at a temperature higher than 500°C and located outside the reduced cross-section; Notwithstanding, that in the simplified calculation method, "Isotherm 500°C," is assumed that the concrete with temperatures higher than 500°C is damaged and does not contribute to the bearing capacity of the element, it is partially retained strength characteristics;

- columns with a square cross-section and four longitudinal rebar at the corners of the section are discussed;

- cylindrical compressive strength of concrete is;

- tensile strength of concrete is ignored;

- area of longitudinal reinforcement embedded outside of the area of splicing is where is the cross sectional area of the concrete;

- the method is valid for the reinforced concrete columns with a minimum width of the cross section, according to [1].

Fig. 3. Biaxial bending of a square column: a) three-dimensional view; b) bending about axis Y; c) bending about axes Y and Z; d) bending about axis Z [8]

Fig. 4. Normalized interaction curve of a square reinforced concrete section with all-sided fire exposure, reinforced with four longitudinal rods class B420 at the corners and d1 ^ / h^ = —0,075

Conclusions. After analyzing the established methodology and the attached normalized interaction curves, the following conclusions can be made:

a) the method is applicable to precast or monolithic square column sections, subjected to biaxial bending and four side fire exposure;

b) normalized interaction curves can be composed of different d1 ^ / h^ (0,000; -0,025; -

0,050;...; -0,200) and different classes of reinforcing steel (B420, B500 and other);

c) for the center of gravity of the longitudinal reinforcement there are three defined cases of the Isotherm 500°C position:

- when a < a is using normalized interaction curves for square columns, subjected to

biaxial bending at normal temperature presented in [5], [6] and [7]. Parameters dl / h, h , fyd , fcd ,

mEd,y, mEd z and nEd shan be replaced with d,,fi/hfi, f fSy,0, fci,fi, mEi y , mEd zzJl and nEd .

Normalized interaction curves used in fire impact are similar to curves presented in [3] and [4];

- when az = a and az > a is using normalized curves for square columns, composed in this

paper according to the proposed procedure;

d) proposed interaction curves can be applied to the determination of bearing capacity and the calculation of the reinforcement;

e) interaction curves can be used to design sections of columns, subjected to all-sides by standard fire exposure, according ISO834, or any other time heat regimes, which cause similar temperature fields in the fire exposed column;

f) reinforced concrete sections design, by the simplified calculation method "Isotherm 500°C", does not take into account the thermal expansion of material (concrete and reinforcing steel).

REFERENCES

1. БДС EN 1992-1-2:2005 и БДС EN 1992-1-2:2005/ NA - Еврокод 2: Проектиране на бетонни и стоманобетонни конструкции. Част 1-2: Общи правила. Проектиране на конструкции срещу въздействие от пожар.

2. Захариева-Георгиева Б. Проверка за огнеустойчивост на стоманобетонни колони чрез опростения изчислителен метод „Изотерма 500°С" на БДС EN 1992-1-2:2005, „сп. Строителство", бр. 6, 2012 г.

3. Нешев Хр. Огнеустойчивост на правоъгълни стоманобетонни колони със симетрична армировка, подложени на огъващ момент и осова натискова сила при едностранно пожарно въздействие в равнината на огъващия момент, Първа научно- приложна конференция с международно участие. Стоманобетонни конструкции теория и практика- София, 2015г.;

4. Нешев Хр., Огнеустойчивост на правоъгълни стоманобетонни колони със симетрична армировка, подложени на огъващ момент и осова натискова сила при четиристранно пожарно въздействие, Първа научно- приложна конференция с международно участие. Стоманобетонни конструкции теория и практика- София, 2015г.;

5. Николов П. Стоманобетонни пътни мостове. Ръководство за проектиране, София, 2013г.

6. Русев К. Стоманобетон НПБСК-ЕС2, София, 2008г.

7. Русев К., В.Янчев ЕС2. Оразмеряване на стоманобетонни конструкции по нормални сечения, София, 2011г.

8. Charif A. Biaxial bending in columns

9. http://faculty.ksu.edu.sa/charif/Documents/Columns-Biaxial.pdf

THE INFLUENCE OF THE STIFFNESS COEFFICIENT OF THE HYDRAULIC LIQUID ON THE DYNAMICAL BEHAVIOUR OF THE SYSTEM "HYDRAULIC CYLINDER -

LOAD"

PhD. Petkov Boris

Bulgaria, Sofia, University of Transport "Todor Kableshkov"

Abstract. In this paper we suggest a way how to determine the stiffness coefficient of the hydraulic liquid in a hydraulic cylinder under load and we also show its influence on the dynamical properties and behavior of the system "hydraulic cylinder- load".

Keywords: stiffness coefficient, hydraulic powered system, frequency response.

INTRODUCTION. During the calculation of the parameters of the hydraulic powered systems the elastic properties of the liquid are usually ignored. In practice, a stiff system is most often required

i Надоели баннеры? Вы всегда можете отключить рекламу.