Научная статья на тему 'Optimize the performance of electrical equipment in gas separation stations (degassing station ds ) and electrical submersible pumps of oil equipment for oil Rumaila field'

Optimize the performance of electrical equipment in gas separation stations (degassing station ds ) and electrical submersible pumps of oil equipment for oil Rumaila field Текст научной статьи по специальности «Электротехника, электронная техника, информационные технологии»

CC BY
233
65
i Надоели баннеры? Вы всегда можете отключить рекламу.
Ключевые слова
ELECTRIC SUBMERSIBLE PUMPS / POWER CORRECTION / DEGASSING STATION / ACTIVE POWER FILTERS / HYBRID FILTERS

Аннотация научной статьи по электротехнике, электронной технике, информационным технологиям, автор научной работы — Abdulhy Al-Ali Majid Abdulhameed, Kornilov V. Yu., Gorodnov A. G.

Annotation: There are various types of electrical equipment used in the extraction of oil at the Rumaila field, with an average voltage of 11 kV and a low voltage of 0.4 kV. The most common elements in this class are transformers and reactors, engines and gas discharge lamps. All of this equipment consumes reactive power and reduces the value of the power factor. (Power factor is the ratio of kW to kVA). The closer the power factor to the maximum possible value of 1, the greater the benefit for the consumer and supplier. In case of low power factor, the current will be increased, and this high current will lead to (large line losses, an increase in the nominal total power of kVA and overhaul dimensions of electrical equipment, deterioration in voltage regulation process and an increase in voltage drop, a decrease in efficiency).Power factor improvement allows the use of smaller transformers, switchgear and cables, etc. as well as reducing power losses and voltage drop in an installation. Improving the power factor of an installation requires a bank of capacitors which acts as a source of reactive energy. These arrangements provide reactive energy compensation. In Rumila, An improvement of the power factor of an installation presents several technical and economic advantages, notably in the reduction of electricity bills, we save (685.854.007 Iraqi Dinar= 550.000 $) for one month . All this work takes 6 to 12 month.

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

Текст научной работы на тему «Optimize the performance of electrical equipment in gas separation stations (degassing station ds ) and electrical submersible pumps of oil equipment for oil Rumaila field»

[МЖ^Н

УДК 621.3.072

OPTIMIZE THE PERFORMANCE OF ELECTRICAL EQUIPMENT IN GAS SEPARATION STATIONS (DEGASSING STATION DS ) AND ELECTRICAL SUBMERSIBLE PUMPS OF OIL EQUIPMENT FOR OIL RUMAILA FIELD

Majid Abdulhameed Abdulhy Al-Ali1, V.Yu. Kornilov2, A.G. Gorodnov3

1Rumaila Operating Organization, Basra, Iraq 2Kazan State Power Engineering University, Kazan, Russia 3Kazan National Research Technical University named after A. N. Tupolev - KAI, Kazan,

Russia

Annotation: There are various types of electrical equipment used in the extraction of oil at the Rumaila field, with an average voltage of 11 kV and a low voltage of 0.4 kV. The most common elements in this class are transformers and reactors, engines and gas discharge lamps. All of this equipment consumes reactive power and reduces the value of the power factor. (Power factor is the ratio of kW to kVA). The closer the power factor to the maximum possible value of 1, the greater the benefit for the consumer and supplier. In case of low power factor, the current will be increased, and this high current will lead to (large line losses, an increase in the nominal total power of kVA and overhaul dimensions of electrical equipment, deterioration in voltage regulation process and an increase in voltage drop, a decrease in efficiency).

Power factor improvement allows the use of smaller transformers, switchgear and cables, etc. as well as reducing power losses and voltage drop in an installation. Improving the power factor of an installation requires a bank of capacitors which acts as a source of reactive energy. These arrangements provide reactive energy compensation. In Rumila, An improvement of the power factor of an installation presents several technical and economic advantages, notably in the reduction of electricity bills, we save (685.854.007 Iraqi Dinar= 550.000 $) for one month . All this work takes 6 to 12 month.

Keywords: electric submersible pumps, power correction, degassing station, active power filters, hybrid filters.

DOI: 10.30724/1998-9903-2018-20-11-12-141-145.

For citation: Majid Abdulhameed Abdulhy Al-Ali, V.Yu. Kornilov, A.G. Gorodnov. Optimize the performance of electrical equipment in gas separation stations (degassing station DS) and electrical submersible pumps of oil equipment for oil Rumaila field. Proceedings of the higher educational institutions. ENERGY SECTOR PROBLEMS. 2019. vol. 21. № 1-2. pp. 141-145. DOI:10.30724/1998-9903-2018-20-11-12-141-145.

INTRODUCTION

Correction power factor for oil stations.

Oil production is operated by Rumaila Operating Organisation, with 14 degassing stations (Gases Separating stations) currently installed 7 in the North field and 7 in the South field. These stations provide 3-phase separation (oil, water & natural gas). Crude oil is sent by pipeline to local refineries or ports in Basra for export. Natural gas is provided to the Basra Gas Company. Water is disposed into disposal wells. Adding that there are 10 injection water stations.

Degassing station (Gases Separating stations) names:

npoôneMbi энергетики, 2019, moM 21, № 1-2

• North Rumaila: DS1, DS2, DS3, DS4, DS5, NIDS, SIDS

• South Rumaila: Markezia (Rumaila), Janubia , Shamyah, Qurainat, Mishrif Shamyah, Mishrif Qurainat, Ratqa.

All this Gases Separating stations DS that feed by electrical supplies from ministry of Iraq electrical (132 KV TO 11 KV). Accordingly this DS will distributor the electrical power to feed electrical submersible pumps and the other equipment which oil production sharing.

Most of these electrical loads are inductive loads, that mean power factor is lagging and these low value. As the reading of power sources, we read the value of power factor value 0.6 to 0.65. Schedule (1). If we assume corrected the power factor to 0.9.

Schedule 1

Electrical power consumption in Gases Separating stations (Degassing station DS)

Rumaila Name of Consumers Monthly Monthly Expected

electricity related to consumption of consumption of consumption of

metering electricity active electricity, total electricity, total electricity

stations metering station kW*h kVA*h for a month after compensation (cos^ = 0.9), kVA*h

North Rumaila CPS1 (T1) CPS1 1782000 2921000 1980000

CPS1 (T2) CPS1 2126000 3429000 2362222

CPS2 (T1) CPS2, CS5 18000 29000 20000

CPS2 (T2) CPS2, CS5 4725000 7875000 5250000

CPS3 (T1) CPS3,DS5 3079000 5048000 3421111

CPS3 (T2) CPS3,DS5 19000 31000 21111,11

CPS4 CPS4 6828000 10668000 7586667

CPS5 (T1) CPS5, CS2, 868000 1335000 964444,4

CPS5 (T2) CPS5, CS2, 5137000 8026000 5707778

CPS9 CPS9 28000 44000 31111,11

CS4 CS4, DS4, NIDS 1431000 2271000 1590000

DS2 (T1) DS2, SIDS 298000 473000 331111,1

DS2 (T2) DS2, SIDS 4000 6000 4444,444

Old Rum (T1) DS1,DS3 1630000 2587000 1811111

Old Rum (T2) DS1,DS3 1038000 1622000 1153333

South Janubia Janubia CS,

Rumaila Janubia DS, Ratga DS 673200 1085800 748000

Markzia Markzia CS, Markzia DS 1302400 2019200 1447111

Shamia Shamia CS, Shamia DS 360800 572700 400888,9

M. Shamia M. Shamia DS 66000 105000 73333,33

Qurinat (T1) Qurinat CS, Qurinat DS, 245000 376000 272222,2

Qurinat (T2) Qurinat CS, Qurinat DS, 1560000 2399000 1733333

M. Qurinat M. Qurinat DS 2100 3300 2333,333

Total 33220500 52926000 36911667

Correction power factor electrical submersible pumps.

The electrical submersible pumping systems deliver an effective and economical means of lifting large volumes of fluids from great depths under a variety of well conditions. The ESP system is comprised of an electric motor, seal section, rotary gas separator optional, multistage centrifugal pump, electric power cable, motor controller and transformers fig (1). ESP is a very versatile artificial lift method and can be found in operating.

Fig. 1. Electrical submersible pump components

A high power factor allows the optimization of the components of an installation. Overating of certain equipment can be avoided, but to achieve the best results, the correction should be effected as close to the individual inductive items as possible. [1-4] The installation of a capacitor bank can avoid the need to change a transformer in the event of a load increase, the reactive power absorbed by a transformer cannot be neglected, and can amount to (about) 5% of the transformer rating when supplying its full load. Compensation can be provided by a bank of capacitors. In transformers, reactive power is absorbed by both shunt (magnetizing) and series (leakage flux) reactance[5-8]. Complete compensation can be provided by a bank of shunt-connected LV capacitors. Individual motor compensation is recommended where the motor power (kVA) is large with respect to the declared power of the installation.

Capacitors are especially sensitive to harmonic components of the supply voltage due to the fact that capacitive reactance decreases as the frequency increases[9-12]. In practice, this means that a relatively small percentage of harmonic voltage can cause a significant current to flow in the capacitor circuit. The presence of harmonic components causes the (normally sinusoidal) wave form of voltage or current to be distorted, the greater the harmonic content, the greater the degree of distortion. If the natural frequency of the capacitor bank power-system reactance combination is close to a particular harmonic, then partial resonance will occur, with amplified values of voltage and current at the harmonic frequency concerned. In this particular case, the elevated current will cause overheating of the capacitor, with degradation of the dielectric, which may result in its eventual failure. Several solutions to these problems are available. This can be accomplished by [13-18]

a. Shunt connected harmonic filter and/or harmonic-suppression reactors or

b. Active power filters or

c. Hybrid filters

Research Issues

Iraq is suffering from electricity power lack ,As summer temperatures go up each spring, wherefore demand of power its increase too ,as the oil stations consider the most consumption of electrical power and it need continual power , we must be find the reduce

143

npo6neMbi энергетики, 2019, moM 21, № 1-2

consumption methods. Power factor correction one of this method .where we get the gain 60

MW extra fig. (2).

12 3

Fig. 2.represented the electrical power consumption(VA)

AIMS

In general, the equipment that working in oil industry have to heavy duty and high ability and works at hard condition. Correcting power factor will be improve the performance of this equipment, add that the reduce electricity bills expense where we are get the gain 550.000 $ at one month.

OBJECTIVES

This research will be to resolve more problems attached to:

Reduction in the cost of electricity.

Technical/economic optimization.

There more of utility will be usefulness (oil and electrical ministry), and this project was achieved by add power factor correction equipment( capacitors and filtering ), with calculated the harmonics action on the grid( the third and five harmonic ).

METHODOLOGY

The steps proposed to complete the research represented by the correction should be effected as close to the individual inductive items as possible as :

Compensation at the terminals of a transformer.

Compensation to increase the available active power output or Compensation of reactive energy absorbed by the transformer.

Power factor correction of induction motors Connection of a capacitor bank and protection settings.

Lighting and electronic devices as soft starting and variable frequency speed .connect directly with the Capacitor elements. Protection, control devices and connecting cables.

Collect and analyse the data by taking the read of kwh meters at every station.

References

1. Badrzadeh D., Smith K., Wilson R. Designing passive harmonic filters for an aluminum smelting plant. - IEEE trans. on industry applications. 2011, Vol. 47, No 2, pp. 973983.

2. Chen Y.-M. Passive filter design using genetic algorithms. - IEEE transactions on industrial electronics, Vol. 50, No. 1, 2003, pp. 202-207.

3. Cirrincione M., Pucci M., Vitale G., Miraoui A. Current harmonic compensation by a single-phase shunt active power filter controlled by adaptive neural filtering. - IEEE trans. on

Industrial Electronics, Vol. 56, No. 8, 2009, pp. 3128-3143.

4. De Lima Tostes M., Bezerra U., Silva R. Impacts over distribution grid from the adoption of distributed harmonic filters on low-voltage customers. - IEEE transactions on power delivery, vol. 20, No. 1, 2005, pp. 384 - 389.

5. Fujita H., Akagi H. Voltage-regulation performance of a shunt active filter intended for installation on a power distribution system. - IEEE trans. on power electronics, Vol. 22, No. 3, 2007, pp. 1046-1053.

6. Ginn H. L., Czarnecki L. S. An optimization based method for selection of resonant harmonic filter branch parameters. - IEEE transactions on power delivery, Vol. 21, No. 3, 2006, pp. 1445-1451.

7. Hamadi A., Rahmani S., Al-Haddad K. A hybrid passive filter configuration for VAR control and harmonic compensation. - IEEE transactions on Industrial Electronics, Vol. 57, No. 7, 2010, pp. 2420- 2434.

8. He N., Xu D., Huang L. The application of particle swarm optimization to passive and hybrid active power filter design. - IEEE transactions on industrial electronics, Vol. 56, No. 8, 2009, pp. 2841-2851.

9. Karimi H., Karimi-Ghartemani M., Iravani M. An adaptive filter for synchronous extraction of harmonics and distortions. IEEE transactions on power delivery, Vol. 18, No. 4, 2003, pp. 1350-1355.

10. Klempka R. A new method for the C-type passive filter design. - Przeglad Elektrotechniczny, 2012, NR 7f, pp. 277-280.

11. Morsi W., El-Hawary M. Defining power components in nonsinusoidal unbalanced polyphase systems: the issues. - IEEE transactions on Power delivery, Vol. 22, No. 4, 2007, pp. 2428-2438.

12. Nassif A. D., Xu W., Freitas W. An investigation on the selection of filter topologies for passive filter applications. - IEEE transactions on Power De- livery, Vol. 24, No. 3, 2009, pp. 1710-1718.

13. Rivas D., Moran L., Dixon J., Espinoza J. Improving passive filter compensation performance with active techniques. - IEEE trans. on industrial electronics, Vol. 50, No. 1, 2003, pp. 161-169.

14. Tan P-C., Morrison R. E., Holmes D. Voltage form factor control and reactive power compensation in a 25-kV electrified railway system using a shunt active filter based on voltage detection. - IEEE trans. on industry applications, Vol. 39, 2003, No. 2, pp. 575-581.

15. Yazdani D., Bakhshai, Jain P. A three-phase adaptive notch filter- based approach to harmonic/reactive current extraction and harmonic decomposition. - IEEE trans. on power electronics, Vol. 25, No. 4, 2010, pp. 914-923.

16. El-gammal, M. A. Dynamic Voltage Restorer ( DVR ) for Voltage Sag Mitigation / M. A. El-gammal, A. Y. Abou-ghazala, T. I. El-shennawy // Int. J. Electr. Eng. Informatics. -2011. - Vol. 3. - № 1. - P. 1-11.

Authors of the publication Majid Abdulhameed Abdulhy Al-Ali - Rumaila Operating Organization, Basra, Iraq. Vladimir Yu Kornilov - Kazan State Power Engineering University, Kazan, Russia.

Anton G. Gorodnov - Kazan National Research Technical University named after A. N. Tupolev - KAI, Kazan, Russia.

Поступила в редакцию 03 декабря 2018 г.

iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.