Научная статья на тему 'Methodology for assessment the possibility of transfer six-phase power line into the mode of operation with incomplete number of phases'

Methodology for assessment the possibility of transfer six-phase power line into the mode of operation with incomplete number of phases Текст научной статьи по специальности «Электротехника, электронная техника, информационные технологии»

CC BY
73
13
i Надоели баннеры? Вы всегда можете отключить рекламу.
Ключевые слова
ELECTRICAL LINES WITH SELF-COMPENSATION AND CONTROLLED SELF-COMPENSATION / INCOMPLETE NUMBER OF PHASES / SIX SYMMETRICAL COMPONENTS

Аннотация научной статьи по электротехнике, электронной технике, информационным технологиям, автор научной работы — Kiorsak M.V., Turturica N.N.

In electric power systems due to various reasons: short circuits, phase breaks, ice melting, phase-by-stage repair of a high-voltage power line (transmission line), interruptions in the power supply to the consumer occur. On single-sided power lines, this leads to a prolonged shutdown of consumers, and to a significant emergency lack of electricity supply. Switching the line to operation with incomplete number of phases significantly increases the reliability of consumes power supply. For double-circuit power lines it is always possible to keep in work at least two phases out of six. Among the various options for double-circuit power lines, the so-called self-compensating and controlled self-compensating high-capacity power transmission lines (SCL and CSCL) were proposed. For unidirectional power supply lines, these cases are accompanied by a prolonged shutdown of consumers from the electrical energy and a long time with a lack of supply. The article is devoted to the methodology for calculation the throughput of SCL and CSCL, which operate with incomplete number of phases. The methodology is based on the use of six symmetric components of currents and voltage of the SСL (СSС) and can be extended and applied in principle to any six-phase power transmission lines, in particular, two-circuit conventional power lines. The equivalents substitution complex schemes in the coordinates of the six symmetrical components in the MATLAB program are modeled. This allows us to find the currents and transmitted power through the line and voltages in the nodes of the network and evaluate the possibility of its operation in this mode.

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

Методика оценки возможности перевода шестифазной ЛЭП в неполнофазный режим работы

В электроэнергетических системах в силу различных причин: коротких замыканий, обрывов фаз, плавки гололёда, пофазный ремонт высоковольтной линии электропередачи (ЛЭП) возникают перерывы в электроснабжение потребителей. Переключение линии с односторонним питанием в неполнофазный режим существенно увеличивает надежность электроснабжения потребителей. Особенно это эффективно для двухцепных ЛЭП. Для них всегда есть возможность сохранить из шести фаз хотя бы две фазы в работе для обеспечения непрерывности энергснабжения. Среди различных вариантов двухцепных ЛЭП были предложены и так называемые самокомпенсирующиеся и управляемые самокомпенсирующиеся линии электропередачи повышенной пропускной способности (СВЛ и УСВЛ). Целью работы является разработка методики расчета пропускной способности шестифазной ЛЭП на примере СВЛ и УСВЛ, которые работают в неполнофазном нагрузочном режиме. Для достижения поставленной цели использовалась методика, основанная на использование шести симметричных составляющих токов и напряжений СВЛ (УСВЛ) при различных несимметричных режимах и которая может быть распространена и применена в принципе к любым видам шестифазным ЛЭП, в частности, к двуцхцепным обычным ЛЭП. Аналогично общеизвестному методу трехфазных симметричных составляющих использованный для оценки возможности перевода трехфазной ЛЭП в неполнофазный режим, метод шестифазных симметричных составляющих позволяет существенно упростить расчёт. Наиболее важным результатом в данной работе является рассмотренная методика расчета электрических величин (токов и напряжений) при неполнофазном режиме СВЛ на основе граничных условий для участка повреждения ЛЭП. Значимость результатов состоит в получении эквивалентной комплексной схемы замещения для обрыва фазы в координатах шести симметричных составляющих, что позволяет найти токи (мощности) шестифазной ЛЭП и напряжения в узлах сети и оценить возможность её работы в неполнофазном режиме.

Текст научной работы на тему «Methodology for assessment the possibility of transfer six-phase power line into the mode of operation with incomplete number of phases»

Methodology for Assessment the Possibility of Transfer Six-Phase Power Line into the Mode of Operation with Incomplete Number of Phases

Kiorsak M.V., Turturica N.N.

Technical University of Moldova

Chisinau, Republic of Moldova

Abstract. In electric power systems due to various reasons: short circuits, phase breaks, ice melting, phase-by-stage repair of a high-voltage power line (transmission line), interruptions in the power supply to the consumer occur. On single-sided power lines, this leads to a prolonged shutdown of consumers, and to a significant emergency lack of electricity supply. Switching the line to operation with incomplete number of phases significantly increases the reliability of consumes power supply. For double-circuit power lines it is always possible to keep in work at least two phases out of six. Among the various options for double-circuit power lines, the so-called self-compensating and controlled self-compensating high-capacity power transmission lines (SCL and CSCL) were proposed. For unidirectional power supply lines, these cases are accompanied by a prolonged shutdown of consumers from the electrical energy and a long time with a lack of supply. The article is devoted to the methodology for calculation the throughput of SCL and CSCL, which operate with incomplete number of phases. The methodology is based on the use of six symmetric components of currents and voltage of the SCL (CSC) and can be extended and applied in principle to any six-phase power transmission lines, in particular, two-circuit conventional power lines. The equivalents substitution complex schemes in the coordinates of the six symmetrical components in the MATLAB program are modeled. This allows us to find the currents and transmitted power through the line and voltages in the nodes of the network and evaluate the possibility of its operation in this mode.

Keywords: electrical lines with self-compensation and controlled self-compensation; incomplete number of phases; six symmetrical components. DOI:10.5281/zenodo.3723643 UDC: 621.315.1

Metodologie pentru evaluarea posibilitatii transferului unei linii electrice cu sase faze în regim de

functionare cu numarul necomplet de faze

Chiorsac M. V., Turturica N.N.

Universitatea Tehnicâ a Moldovei Republica Moldova

Rezumat. În sistemele electroenergetice din diferite motive ca scurtcircuite, rupri a faze, topirea ghetii, reparatie pas cu pas a unei linii de înaltâ tensiune (linie de transmisie), se produc întreruperi în alimentarea consumatorilor. Obiectivul lucrârii este de a dezvolta o metodologie pentru calcularea debitului unei linii de transmisie a energiei cu sase faze, luând ca exemplu linii electrice cu autocompensare si de tip LEDA, care functioneazâ într-un regim de sarcinâ cu numâr necomplet de faze. Pentru a atinge acest obiectiv, am folosit o tehnicâ bazatâ pe utilizarea a sase componente simetrice ale curentilor si tensiunilor LEC (LEDA) pentru diferite regimuri asimetrice si care poate fi distribuitâ si aplicatâ în principiu la orice tip de linii de alimentare cu sase faze, în special, la liniile de alimentare conventionale cu dublu circuit. În mod similar cu metoda binecunoscutâ a componentelor simetrice trifazice, utilizatâ pentru a evalua posibilitatea transferârii unei linii de alimentare trifazate într-un regim incomplet de faze, metoda componentelor simetrice cu sase faze poate simplifica semnificativ calculul. Cel mai important rezultat al acestei lucrâri o prezintâ metoda de calculul al parametrilor electrici (curenti si tensiuni) în cazul unui regim de functionare ce numâr necomplet de faze , utilizând conditiile de limitâ pentru portiunea avariatâ a liniei electrice de transmisie. Semnificatia rezultatelor consta în obtinerea unui scheme complexe echivalente la ruperea fazei în coordonatele fazore a sase componente simetrice, ceea ce permite de a calcula curentii (puterile) si tensiunii unei linii de transmisie cu sase faze în nodurile retelei, ce permite estimarea posibilitâtii functionârii acestei linii în regim de fazâ incomplet.

Cuvinte cheie: linii electrice cu autocumpensare si linii electrice diríjate, functionare cu numâr incomplet de faze, sase componente simetrice.

© Kiorsak M.V., Turturica N.N., 2019

Методика оценки возможности перевода шестифазной ЛЭП в неполнофазный режим работы.

Киорсак М.В., Туртурика Н.Н.

Технический университет Молдовы Кишинев, Республика Молдова Аннотация. В электроэнергетических системах в силу различных причин: коротких замыканий, обрывов фаз, плавки гололёда, пофазный ремонт высоковольтной линии электропередачи (ЛЭП) возникают перерывы в электроснабжение потребителей. Переключение линии с односторонним питанием в неполнофазный режим существенно увеличивает надежность электроснабжения потребителей. Особенно это эффективно для двухцепных ЛЭП. Для них всегда есть возможность сохранить из шести фаз хотя бы две фазы в работе для обеспечения непрерывности энергснабжения. Среди различных вариантов двухцепных ЛЭП были предложены и так называемые самокомпенсирующиеся и управляемые самокомпенсирующиеся линии электропередачи повышенной пропускной способности (СВЛ и УСВЛ). Целью работы является разработка методики расчета пропускной способности шестифазной ЛЭП на примере СВЛ и УСВЛ, которые работают в неполнофазном нагрузочном режиме. Для достижения поставленной цели использовалась методика, основанная на использование шести симметричных составляющих токов и напряжений СВЛ (УСВЛ) при различных несимметричных режимах и которая может быть распространена и применена в принципе к любым видам шестифазным ЛЭП, в частности, к двуцхцепным обычным ЛЭП. Аналогично общеизвестному методу трехфазных симметричных составляющих использованный для оценки возможности перевода трехфазной ЛЭП в неполнофазный режим, метод шестифазных симметричных составляющих позволяет существенно упростить расчёт. Наиболее важным результатом в данной работе является рассмотренная методика расчета электрических величин (токов и напряжений) при неполнофазном режиме СВЛ на основе граничных условий для участка повреждения ЛЭП. Значимость результатов состоит в получении эквивалентной комплексной схемы замещения для обрыва фазы в координатах шести симметричных составляющих, что позволяет найти токи (мощности) шестифазной ЛЭП и напряжения в узлах сети и оценить возможность её работы в неполнофазном режиме.

Ключевые слова: самокомпенсирующиеся и управляемые самокомпенсирующиеся линии электропередачи, неполнофазный режим, шесть симметричных составляющих.

INTRODUCTION

To increase the transmission capacity of electrical lines, the use of a new generation of high-capacity transmission lines has been proposed, including electrical lines with self-compensation (SCL) and controlled electrical lines with self-compensation (CSCL) [1-4]. The introduction of these power lines in practice requires solving a whole range of problems such as relay protection (RP) from various damages, including short circuits (SC), phase ruptures (PhR) and analysis of the possibility of their operation with incomplete number of phases (INPh).

Of all the possible short circuits on the SCL or CSCL, more than 60% of the short circuits belongs to short circuits of single-phase followed by disconnecting the line. For consumers connected via SCL or CSCL to a single source of electricity, this will interrupt the supply of electricity. The power supply of the consumers can be maintained by disconnecting only the damaged phase, if each phase of the SCL or CSCL has its own switch. Operation SCL and CSCL with no-full number of phases (NFPh) can be provided as a possibility that significantly increases the reliability of the electrical system,

for example, when carrying out phase-by-phase repair of power lines or step by step phase ice melting.

In order to estimate what power of electricity can be transmitted to consumers, it is necessary to study the operation of the power line (SCL or CSCL) without the disconnected phase.

For the calculations of the maximum value of the electrical power transmitted by the three-phase conventional power lines [5] in the INPh operating modes, the method of three symmetrical components 0,1,2 is used. [6-24]. Similarly, for calculating the maximum value of the electrical power transmitted by SCL or CSCL in the INPh asymmetric mode of operation, the method of six symmetrical 0,1,2,3,4,5 components can be used. This requires the following data:

- the equivalent substitution schemes of the electrical network and all its elements for the sequences 0,1,2,3,4 and 5 of the currents and voltages;

- the maximum values of the power of the consumers connected to the transformer stations of the electrical network;

- passport data for generators of the power plants.

I. DETERMINATION OF THE MAXIMUM TRANSMISSION POWER IN THE MODE OF OPERATION WITH INCOMPLECT NUMBER OF PHASES (INPh)

The methodology for assessing the maximum value of the transmitted power by SCLor CSCL is based on the following assumptions: similar to asymmetric load calculations by using three symmetrical components, it is considered, that the voltage of the second (2) and fifth (5), as well as the first (1) and fourth (4) sequences of the voltage at the terminals of all power consumers connected to the common distribution network are equal. Therefore, in most cases it is sufficient to determine the asymmetry voltage on the transformer busbars of the substations, connected to the line operating in the INPh mode. The entire load is replaced by an equivalent one and is brought to the busbars of the corresponding voltage of each of the substations connected to the line operating in the INPh. Considering SŒ (CS^) as six-phase power lines, for calculating asymmetrical short-circuits, ruptures of the phases and for calculating the maximum value of the transmitted power through them in the INPh

mode of operation by using six symmetrical components it is necessary:

- asymmetric systems of voltages, currents and EMF to be present as the sum of the corresponding symmetrical components;

- the initially asymmetric equivalent circuit shall be represented by six symmetrical equivalent circuits of sequences 0,1,2,3,4 and 5 of currents. The number and types of the symmetrical components circuits depends on given analyzing type of asymmetry;

- for given type of asymmetry, according to symmetric equivalent circuits, symmetric components of currents and voltages are calculated;

- using the calculated symmetrical components, the desired currents and voltages in the original circuit are determined.

In accordance of deterioration type, equivalent circuits of individual symmetrical components can be obtained (Fig.1). Figure 1 shows the circuits of the symmetrical components of the CSC line when the phase A is ruptures and shifting angle between voltages vectors of the phases closely placed of the CSC 6 = 0 °

UoMN

a)

Z1M , „ U.1MN ,

Z2M M HZ3

U2MN

Z2N CZh

d)

Z3M U3MN Z3N

"1 Z3M t t Z3N (-

I3y

b)

-, U4MN -,

E4M Z4M hA ^ Z4N

E4n

I4y

C) U5MN

Z5M ^^NN

Fig. 1. The equivalent circuits of symmetrical components for ruptured phase of the CSCL with angle 0 = 0 a- for zero sequence; b -for third sequence; c - for first and fourth sequences; d - for the twice and

fifth sequences.

The ruptured phase A can be considered undamaged if a UMN source with the equivalent voltage equal to the potential difference between the rupturing points is included between the breaking points M and N. The phase components of the currents and voltages at the breaking point are characterized by the relations:

Taking into account the boundary conditions expressed in to the six symmetrical components, the equivalent schemes of individual sequences can be combined into a complex equivalent

circuit. The schemes of individual components are connected in parallel to the damaged place. The individual sequence schemes need to be connected in such a way that the sum of the currents is equal to zero and the voltages of the individual sequences are equal between them. As an example, fig. 2 shows the complex equivalent scheme of the line in to the symmetric components in the MATLAB program, when phase A is ruptured.

Fig. 2. Complex equivalent scheme of the line in to the symmetric components for the ruptured phase A

in the MATLAB program.

II. CALCULATION THE MAXIMAL TRANSMITION POWER THROUGH HV LINE WHICH WORKS WITH INCOMPLETE NUMBER OF PHASES

Using the method of six symmetrical components, the phase and line currents and voltages according to the relations are determine

Or in a simplified form F = Fe-Fs

fa 1 1 1 1 1 1

fb 1 ejm eJ240 eJ180 e 120 eJ60

f 1 eJ24° eJ120 1 e 240 eJ120

f fe ff 1 ejm 1 1 eJ180

1 ejno 1 ejW ej™ ej™ 1 efl«> ej™ eJ*o eJ™ eJ™

(1)

S6--

1 1 1 1 1

eJ 300 eJ 240 eJ 180 e 120 eJ 60

eJ24° e 120 1 eJ 240 eJ 120

eJ1S0 1 e 180 1 eJ 180

eJ 120 eJ 240 1 e 120 eJ 240

eJ 60 e 120 e 180 eJ 240 e 300

(2)

the square transition matrix from the six symmetrical components 0,1,2,3,4,5 of the vectors of current (voltage) to the six-phase coordinates A, B, C, D, E, F of the line

F =

Fa Fa

Fb Fa

Fc Fa

; Fs =

Fd Fa

Fe Fa

Ff Fa

Where F column matrix of current (voltage) vectors in the phase coordinates, Fs column matrix of current (voltage) vectors in the six symmetrical components.

Converting the vectors using the give up matrixes is advisable for calculations in the MathCad system, because this allows for calculating the required currents and voltages without write separate formulas. On the base of the equivalent circuits of six 0, 1, 2, 3, 4 and 5 sequences (fig. 1) and complex equivalent circuit (fig. 2), following system of equations can be writes:

z0/0+[/0 = o

Z3I3+U3= 0

Zjt + Ut=Et

U0 +11, ■ej60+U1 -e'm +U3 +[/4-e'm +U5-ejm = 0 Ü0 +Ü1 ■e'm+Ü1 -e'm +Ü3 +Üt-e'm +Ü5 ■e'm = 0 [/0-[/,+[/2-[/3+[/„-[/,= 0

(3)

U0 +Ul-e~'m +U2-e~'m -

■U.J+Ui -e'1™ + IJi -e'm = 0

Here Zo, Zi, Z2, Z3, Z4, Z5 are the resulting impedances of the circuits of the six symmetrical components in relation to the rupture point. The first six equations of the system are compiled according to Kirchhoffs second law (fig.i). The remaining six equations of the system are written according to the conditions at the place of asymmetry. For ruptured phase A , the boundary conditions written through the six symmetric components according to(l): i a = 0. r A ■ = 0. Ûb = 0, ûb ' = 0, ùc = 0, ùc ' = 0. Using the known impedances of the complex equivalent circuit, the symmetric components of currents and voltages in all nodes and branches of the circuit are calculated. The phase and line currents and voltages are calculated by the relations (i). According to the phase and line

values of currents and voltages, power flows for given branches:

*pq *pq *pq *pq *pq *pq

s* =ùpaIa+ ùpbh +ùpcic + mia'+ùpb,h'+ùpic (4)

or

. pq tpq . pq , pq , pq , pq

S"=6\Üfh +Ùpl2 +Ùph +ÙPU +Ùph +Ùph (5),

where p. and q are the beginning and end of a given branch

iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.

The calculation is carried out for the load range from maximum to zero (for example, 100% Sl, 80% Sl, etc.), where Sl is the power on beginning of the line. The loads of the transformers substations vary in proportion to the load on the beginning of the line. At each step, currents and voltages are calculated. In the same way, changing the load in the range from 100% to 20% are built the dependences of Uf on the values of the transmitted power. Following the above calculation method, it is possible to calculate the voltage deviation at all substations of the considered network and construct for each substation the graphs Vi = f (Sl), where

U 100% and b = / (Smp), where

V, =-

s = ^-100% . The analysis of these dependencies

allows us to solve the problem of the maximum value of the transmitted power, based on the criterion of voltage quality at the consumer. As a result of the analysis of these dependencies, the maximum value of the transmitted power through the line is found. Comparing the all results of the analysis is selected the power that satisfies the given technical limitations.

III.CALCULATION THE SHORT CIRCUIT CURRENTS WHEN HV LINE WORKS WITH INCOM-PLECT NUMBER OF PHASES

The asymmetry that occurs during the phase rupture was characterized by the corresponding voltages and currents that can be decomposed into separate sequences. Their values depend on currents and voltages of the previous mode of operation and have a significant effect to the operation of relay protection. In order to ensure the operation selectivity of the relay protection of the line in INPh it is necessary to adjust the relay protection in such a way, that there are

Z,A +U,=K

Z,L+U,=0

ZJ.+U

0

L + L + L + L+lt + L= 0

U0 +U,-e'^+U, - e' +U3 +U, ■e"m +U,-e,wl = 0

capable to operate correctly At the same time, the necessary sensitivity of the relay protection must be ensured during the short circuits, which can occur during operation of the line in the INPh regimes. For the lines which supplies with electrical energy the consumers from one sours, as a rule, are installed the following relay protections:

- current cut-off relay protection, connected to the phase currents and homopolar (zero) sequence currents;

- maximum current relay protections, connected to the phase currents and homopolar (zero) sequence currents.

To choose the start current of the current cutoff protection, it is necessary to know the highest short-circuit currents behind the step-down transformers. To calculate the short-circuit currents on the lines with a single tap may be used the expressions [4]. At the figure 3, the simplified scheme of six-phase line with rupture of the phase on the chain I and phase short circuit on the chain II are given.

j-GD '•-GO

Fig. 3. The short circuit of the one phase on the ground with simultaneous rupture of another phase of

the line.

To check the reliability coefficient of the protection, in most cases, it is necessary to know the currents of a single-phase short circuit of one of the working phases during the operation of the line in the INPh regime. The scheme of fig. 3 in the cases of short circuit. with the simultaneous rupture of one phase is characterized by 24 unknown currents and voltages:

i ik ' ' k ' 14k 'isk'^ok' ' ^2(7 ' ' ^4(7 '^ou'

u2K, U3K, U 4K, U5K, U 0K ,Ulv, U2u, U3u, U4u, U5u, Uou. For each of characteristic sequences, the relationship formulas between voltages and currents it is compiled, taking into account the accepted positive direction of currents and voltages:

-F = -7 I + 7 I -U ■

N IKK IX 1KU lu IK'

-(P —p \=7 7 +7 i -IJ ■

\ M N > IUK IK IUU 1U If/'

" — Z2UKI2K ^2UU^2U ~ U2[I,

0 ~ KK^AK Z4KUI4U — U4K,

(6)

-F 1 -

® ^OKK^OK ^OKU^OU

where Zxkk = Zn, Zxyy = Zx = Zn Zm - self impendences;

ZxKU = ZxUK = ZN - mutual impendences, where x is the index of the sequences (x = 0, 1, 2, 3, 4, 5) The rest of the equations are compiled according to the boundary conditions for places of short circuit and rupture. For the phase A short circuit to ground UAK = o, iA.K = 0, /,,, = 0. /,, , = 0, /,.,. - 0. ic,K = 0 for the phase. A in the rupture point /„. =0, (/,,. =0, (/,,,. =0, UB-O=0, 1)^=0,1)^=0.

To write the equations, we use (1)

^AK = u0K + U1K + u2K + u3K + u4K + u5K ■

i =i +i -e'm+i -e'™-i +/ -eJ1K + +/ -e1™-

/ =/ +/ -em+i -ejm+i +i ■eJ120 + +i -e'm-

K c '

I BK ~ I OK K 14K

i =i +/ -ejm+i -e~jm+i +/ • em +

LCK 10K~11K c 2K c IK AK c ~

+/, K • e'm ;

-cp _/7 \-7 t +7 t -tt

\ M N ) ^5UK1 5K ^ ^5UU1 5U 1

+1 -e' ■

IAU

ÚAV = ÜW + Úla-e^+Ú^-e'™-Ú]a + Ú4a-e>™ + úsa = ú0a + Úm-e-jm + Úla-e-'240 + Ú3a + Üm-e'm +

^'b'u ~ Uou ~ jj + U2jj ~ u3U + UAU — U5u,

(7)

UCIJ=Uw+UlY-e'™+Ulh +Úv,-ejl2°;

>+Um+UáI

Ucv = UW+Ua+ Uia-e^-Um +Um-e"s +

To calculate the symmetric components of the currents and voltages using Mathcad, a matrix of coefficients and a matrix of the free members are compiled. The found currents and voltages of individual sequences in places of short circuit and rupture allow us to find currents and voltages at other points of the original circuit. The symmetrical components in the line from the power supply system N side and current of the phase A are calculated according to found currents and the corresponding equivalent circuits:

Ln=Lk~Lu, where x is the corresponding sequence.

The calculated phase currents and voltages at all points of the network allow to analyze the operation of relay protection and of the conclusions about th e need to change the settings of the operation of the relay protectio, fig. 2. complex equivalent scheme of the line for the ruptured phase a in the matlab program. (as in the usual analysis of the operation of the relay protection).

CONCLUSIONS

1. The supply of the consumers with electrical energy at the single-phase short circuits of the SCL or CSCL followed by the disconnection of the failed phase can be maintained by ensuring their operation with incomplete number of phases.

2. The maximum admissible transmitted power through SCL or CSCL with INPh can be calculated by modeling at the computer the equivalent schemes of the symmetrical hex phase components

References

[1] Postolatij V.M.. Aktual'nye problemy ehnergetiki Respubliki Moldova i puti ih resheniya.[ Actual problems of the energy sector of the Republic of Moldova and their solutions]. Sbornik statej «Up-ravlyaemye ehlektroperedachi», Vyp. 7. «Sis-temnye voprosy,konstruk cii i rezhimy linij peremennogo toka», Kishinev, Shtiinca 1993,pp. 80-96 (In Russian).

[2] Venikov V.A., Astahov Yu.N., Postolatij V.M. Upravlyaemye samokompensiruy ushchiesya linii ehlektroperedachi. [Controlled self-compensating power lines]. Informehnergo, Dep. 1985, pp.20. (In Russian).

[3] Astahov Yu.N., Postolatij V.M., Komendant I.T., Chalyj G.V. Upravlyaemye linii ehlek-troperedachi [Managed power lines]. Kishinev: Shtiinca, 1984. - 296 pages. (In Russian).

[4] Mercel D. Protective Relaying Theory and Applications, , Inc., New York, 2004.

[5] Losev S.B., Chernin A.B. Vichislenie electrich-eskih velichin v nesimmetrichnih regimah elec-tricheskih sistem. [Calculation of electrical values in asymmetric modes of electrical systems], Moscow, 1983, 527 p. (In Russian).

[6] Dunaeva N.V., Kontorovich A.V., Shcherbachev O.V. Metodika rascheta nepolnofaznyh usta-novivshihsya rezhimov slozhnyh ehlektricheskih sistem. [Rezhimy i oborudovanie ehlektricheskih system], -Trudy LPI 1980, № 369. (In Russian).

[7] Averbuh A.M. Primery raschyotov nepolnofaznyh rezhimov i korotkih zamykanij.[ Examples of calculation of out-of-phase modes and short circuits] Leninigrad, 1979. 184 p. (In Russian)

[8] Atabekov G.I. Teoriticheskie osnovy relejnoj zashchity vysokovol'tnyh setej [Theoretical Foundations of Relay Protection of High Voltage Networks]. Leninigrad,1957. 344 p. (In Russian).

[9] Zakaryukin V.P., Kryukov A.V., Modelirovanie predel'nyh rezhimov ehlektricheskih sistem s uchyotom prodol'noj i poperechnoj nesimmetrii [Modeling of limiting modes of electrical systems taking into account longitudinal and transverse asymmetry]. Irkutsk 2006. 139 p. (In Russian).

[10] Chernin A.B. Vychislenie ehlektricheskih velichin i povedenie relejnoj zashchity pri nepolnofaznyh rezhimah v ehlektricheskih sistemah [Calculation of electrical quantities and the behavior of relay protection in non-phase conditions in electrical systems]. Leningrad,1963. 416 p. (In Russian).

[11] T. C. Singh, K. R. Ram and B. V. S. Ram, "Transient stability analysis comparison of double 3-ph to 6-ph converted transmission line for symmetrical and unsymmetrical faults," 2017 International Conference on Power and Embedded Drive Control (ICPEDC), Chennai, 2017, pp. 3237.

[12] Alexandrov G.N., Astakhov Y.N., Venikov V.A. Electric transmission lines of increaset capac-

1 = 1+1 -e' +1 -e

1C'K 1QK ~ hK c ~12K c

e

ityand reduced ecological effect. Session papers & proceedings. Paris, 1982. 6 p.

[13] Gerih V.P., Shtrobel' V.A. Modelirovanie dvuhcepnyh linij ehlektroperedachi s usilennoj ehlektromagnitnoj svyaz'yu mezhdu cepyami [Simulation of double-circuit power lines with enhanced electromagnetic coupling between circuits]. Chelyabinskogo politekhnicheskogo insti-tuta, 1978, pp.134-139(In Russian).

[14] M. A. Laughton, "Analysis of unbalanced polyphase networks by the method of phase coordinates. Part I: system representation in phase frame of reference," Proc. IEEE, vol. 115, no. 8, pp. 163-172, Aug. 1968.

[15] Kulikov, Y.A. Perekhodnye processy v ehlek-tricheskih sistemah [Transients in electrical systems]. Moskva, 2003. 283 p. (In Russian).

[16] Zakaryukin, V.P., Kryukov A.V., Kryukov E.A. Uchet prodol'noj i poperechnoj nesimmetrii pri oprede-lenii predel'nyh rezhimov ehnergosistem [Accounting for longitudinal and transverse asymmetries in determining the limits of power systems] .Ehnergetika: ehkologiya, nadezhnost', bezopasnost'. - Tomsk 2004, pp.154-157(In Russian).

[17] M. F. Abdel-Fattah, A. A. El-Alaily and Z. S. El-Razaz, "Fault resistance investigations for faults in double-circuit double-fed transmission lines," 2016 17th International Scientific Conference on Electric Power Engineering (EPE), Prague, 2016, pp. 1-6.

[18] Popov V.A., Misrihanov M.SH., Kushkova E.I. Opredelenie sostavlyayushchih tokov pri nes-immetrichnyh rezhimah raboty oborudovaniya [Determination of component currents with

asymmetric operating modes of equipment]. Ehnergetik, 2000, №1. (In Russian).

[19] Fortescue C.L. Method of symmetrical coordinates applied to solution pf polyphase network. "Translaction of AIEE", 1918, vol. 33, Pt. 11

[20] B. Bhatt Navin, S. Venkata Subramanian, C. Guyker William, H. Booth William, "6 Ph (Mul-ti-Ph) Power Transmission Systems: Fault Analysis", IEEE Transactions on Power Apparatus and Systems, vol. PAS-96, no. 3, May/June 1977.

[21] "Enhancement of transmission efficiency by 6 ph transmission" in Proceedings of national seminar on "Energy crisis 2000", Arunai Engineering college Tiruvannamalai, pp. 23-24, January 1999.

[22] T. C. Singh, K. R. Ram and B. V. S. Ram, "Transient stability analysis comparison of double 3-ph to 6-ph converted transmission line for symmetrical and unsymmetrical faults," 2017 International Conference on Power and Embedded Drive Control (ICPEDC), Chennai, 2017, pp. 3237.

[23] H. Liao, B. Li, Z. Li, D. Du and X. Jiang, "Zero-sequence voltages of UHV untransposed double-circuit lines and their influence on pilot protection," 2015 5th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), Changsha, 2015, pp. 846-851.

[24] Venkata S.S., Guyker W.C., Booth W.N., Kon-dragunta J. 138-kV, Six-phase Transmission Sys-tems:Fault Analysis. IEEE Transactions on Power Apparatus and Systems, Vol. PAS-101, No. 5, May 1982, pp.1203-1218

Сведения об авторах.

Kiorsak Michael

Dr. habilitat, professor Technical University of Moldova ,Chisinau Moldova Scientific interests analysis of functioning of relay protection of controlled two-chain electric transmission lines

E-mail: [email protected]

Turturica Natalya

Senior Lecturer

Pridnestrovian State

University. Scientific interests are related to the development of a methodology for calculating asymmetric modes of controlled self-compensating power lines E-mail:

natalya [email protected]

i Надоели баннеры? Вы всегда можете отключить рекламу.