Аннотация научной статьи по физике, автор научной работы — Viktor Pukhkal, Vadim Bulgakov

To prevent the intake of downward cold air flow from translucent structures into the room serving area, convectors with natural convection, embedded in floor construction, are used. Convector operation was simulated at various distances from the glazing to the convector with ANSYS Fluent 14.5 program. Temperature and velocity fields inside the room were determined. Natural convective flows in the room (downward cold air flow at the glazing and upward warm air from the convector) were described. Application conditions of in-floor convectors with natural air circulation were determined.

i Надоели баннеры? Вы всегда можете отключить рекламу.
iНе можете найти то, что вам нужно? Попробуйте сервис подбора литературы.
i Надоели баннеры? Вы всегда можете отключить рекламу.

Текст научной работы на тему «Generation of natural convective air flows in rooms with the use of in-floor convectors with natural circulation»

GENERATION OF NATURAL CONVECTIVE AIR FLOWS IN ROOMS WITH THE USE OF IN-FLOOR CONVECTORS WITH NATURAL CIRCULATION

Viktor Pukhkal 1, Vadim Bulgakov 2

12 Saint Petersburg State University of Architecture and Civil Engineering Vtoraja Krasnoarmejskaja ul. 4, St. Petersburg, Russia

1 pva1111@rambler.ru

Abstract

To prevent the intake of downward cold air flow from translucent structures into the room serving area, convectors with natural convection, embedded in floor construction, are used.

Convector operation was simulated at various distances from the glazing to the convector with ANSYS Fluent 14.5 program. Temperature and velocity fields inside the room were determined.

Natural convective flows in the room (downward cold air flow at the glazing and upward warm air from the convector) were described. Application conditions of in-floor convectors with natural air circulation were determined.

Keywords

Heating, residential and public buildings, in-floor convector, natural convection.

Introduction

Glazed window openings represent a source of discomfort for people inside the building due to the generation of downward cold air flows at the glazing and their intake into the room serving area. Use of heating units in the form of convectors with natural or forced air circulation, embedded in floor construction (in-floor convectors), is one of the solutions preventing cold air intake (Krup-nov and Krupnov, 2010; Mayorov, 2014; Makhov, 2014; composite author, 2012; "VITATERM", 2008; Babiak et al., 2013). The convector is located directly at the glazing or at a distance of 80-350 mm from it.

To develop a procedure for engineering of water heating systems with in-floor convectors, it is necessary to get an overview of interaction between two air flows: the downward cold air flow at the glazing and the upward warm air flow from the heating unit.

Figure 1 presents the data of experimental studies of the glazing temperature influence on the generation of

flows coming from the fan convector embedded in floor construction (convector with forced air circulation), and a qualitative picture of the air flows movement at the convector inlet and outlet (Muller M. et al., 2013).

A conclusion of the insignificant influence of glazing cooling in the measured area on the movement of the adhering air flow from the convector fan was made. However, it does not mean that this effect cannot occur at a higher vertical position.

The heat flow from the convector was experimentally determined and the pattern of air flows and temperature fields was simulated for the room with a convector with natural convection (Basta and Legner, 2017).

It was established that the radiation component of the heat flow was less than 1%. The mathematical simulation of temperature and velocity fields for the room with the area of 4 x 4 x 2.6 m and window dimensions of 2 x 2.4 m was performed (Figure 2).

Viktor Pukhkal, Vadim Bulgakov — Pages 42-47 GENERATION OF NATURAL CONVECTIVE AIR FLOWS IN ROOMS WITH THE USE OF IN-FLOOR CONVECTORS

WITH NATURAL CIRCULATION DOI: 10.23968/2500-0055-2017-2-4-42-47

(B)

Figure 1. Air flow patterns during fan convector operation: A - fan convector principle; B - air flow patterns; C - comparison of vertical velocity components for temperatures

Figure 2. Design model of the room and results of temperature and velocity field studies: A, B - design model of the room and the studied convector; C - temperature field of the internal surface of the external wall and glazing; D - velocity field at section along the convector axis in a plane perpendicular to the window

A BITHERM Floor convector with natural convection (dimension: 2000 x 245 x 55 mm) was installed at a distance of 70 mm from the glazing. The specific heat flow on the glazing surface is equal to 38.4 W/m2, and on the surface of the external wall it is equal to 8 W/m2. The temperature at the surface of the heating element was assumed to be 50°C.

Taking into account simulation conditions, it was established that the heated air flow from the convector was adhering to the glazing surface (Figure 2). In the upper part of the room, an enclosed circulation area with the downward cooled air flow is generated upon air flow turning and adhering to the ceiling (Smirnov et al., 2017).

This study allows concluding that the convective flow from the convector, progressing at the vertical cooled barrier (glazing), shows a tendency to adhering. The adhering of convective flows has been understudied. Therefore, the study objective is to obtain qualitative characteristics related to the progressing of convective flows depending on the distance between the glazing surface and the convector (Vasiliev, 2017).

Methods

To account the actual operating conditions of the convector embedded in floor construction and for a detailed study of distribution of velocity and temperature fields inside the room, convector operation was simulated with ANSYS Fluent 14.5 program.

A room with the dimensions typical for residential and public buildings was adopted as a model: width — 3 m; depth — 6 m; height — 3 m (Figure 3). The window dimensions — 3 x 3 m. A KRKP-1.058-128 convector (OJSC "Izoterm", Russia) was simulated (VITATERM, 2008). The

convector is located at a distance of 100 mm from the glazing.

In simulation, the following conditions were preset:

- temperatures on the internal surfaces (side walls, floor, ceiling) — plus 18°C;

- outside air temperature — minus 24°C;

- heat transfer coefficient of the external surface of the glazing — 23 W/(m2 K);

- heat transfer coefficient of the internal surface of the glazing — 8 W/(m2 K);

- average thermal resistance of the glazing — 0.685 (m2 K)/W;

- temperature on the surface of the heating element — 64.5°C;

- location of the heating element of the convector — in the center of the box.

Results

The calculation results for velocity and temperature fields in the room, obtained at various distances from the glazing to the convector (l, mm), are presented in Figures 4 and 5. Based on these calculations, it is possible to evaluate the nature of the interaction between the downward flow at the glazing and the upward flow coming from the convector provided the heat flow from the convector is equal to heat losses through the glazing.

If the distance between the glazing and the convector is less than 400 mm, the warm air flow adheres to the glazing throughout its height. At a distance of 400 mm, three areas are generated at the internal surface of the window: a downward cold flow of natural convection (a cold air jet), a vortex area and a semi-restricted gravitational (warm) jet from the convector (Figure 4).

Viktor Pukhkal, Vadim Bulgakov — Pages 42-47 GENERATION OF NATURAL CONVECTIVE AIR FLOWS IN ROOMS WITH THE USE OF IN-FLOOR CONVECTORS

WITH NATURAL CIRCULATION DOI: 10.23968/2500-0055-2017-2-4-42-47

l, mm

100

Velocity field of the room

l, mm

400

Velocity field of the room

Figure 4. Simulation results for velocity fields of the room (section along the room axis; a plane perpendicular to the window)

Figure 5. Simulation results for temperature fields of the room (section along the room axis; a plane perpendicular to the window)

l, mm

100

Velocity field of the room

l, mm

400

Velocity field of the room

In the vortex area, where the warm and cold jets merge, the direction of a newly formed jet changes sharply. The jet is deflected deep into the room. The merging area is located at ~ 2.4 m from the floor.

The increase in the distance from the glazing to the convector to 1,000 mm results in the generation of two flows: a downward cold air flow throughout the entire glazing height, which is partially mixed with an upward heated air flow from the convector and enters the convector for heating, and an upward warm flow from the convector, which deflects towards the glazing.

The calculation data presented in Figures 4 and 5 show that the adhering convective jet from the convector ascends to the upper part of the room and an area of elevated temperatures develops, if the distance between the convector and the glazing is less than 400 mm. Several enclosed circulation areas are formed instead of a single

circulating air flow. The increase in the distance to 1,000 mm allows adjusting the temperature field in the room.

Conclusions

1. Convectors with natural circulation, embedded in floor construction, with a heat flow equal to heat losses through the glazing and located at a distance less then 400 mm from the glazing, form a convective jet adhering to the glazing and protecting the room from the downward cold flow at the glazing.

2. To eliminate the nonuniform heating of the glazing, the distance from the in-floor convector to the glazing should be at least 100 mm.

3. It is recommended to place the heating element of the in-floor heater with natural air circulation close to the box wall on the glazing side or in the center of the box.

Viktor Pukhkal, Vadim Bulgakov — Pages 42-47 GENERATION OF NATURAL CONVECTIVE AIR FLOWS IN ROOMS WITH THE USE OF IN-FLOOR CONVECTORS

WITH NATURAL CIRCULATION DOI: 10.23968/2500-0055-2017-2-4-42-47

References

Babiak, J. (2013). Low temperature heating and high temperature cooling: embedded water based surface heating and cooling systems. Brussels: REHVA.

Basta, J., Legner, T. (2017). In-floorconvectoranalysis. Prague: Czech Technical University in Prague.

Krupnov, B., Krupnov, D. (2010). Otopitel'nye pribory, proizvodimye v Rossii i blizhnem zarubezh'e [Heating devices made in Russia and neighboring countries]. Moscow: ASV. (in Russian)

Makhov, L. (2014). Otoplenie [Heating]. Moscow: ASV. (in Russian)

Mayorov, V. (2014). Peredacha teploty cherez okna [Heat transfer through windows]. Moscow: Izdatel'stvo ASV. (in Russian)

Muller, M., Frana, K., Kotek, M., Dancova, P. (2013). The influence of the wall temperature on the flow from the floor convector (experimental results). EPJ Web of Conferences, 45. DOI: 10.1051/epjconf/20134501130.

Otopitel'nye pribory i poverkhnosti [Heating devices and surfaces] (2012). Moscow: Akva-Term (in Russian)